46
Typical Setting of the V/f Pattern
Set the V/f pattern according to the application as described below. For
400-V Class Inverters, the voltage values (n10, n13, and n15) should be
doubled. When running at a frequency exceeding 50/60 Hz, change the
Maximum Output Frequency (n09).
Note: Always set the maximum output frequency according to the motor char-
acteristics.
1. For General-purpose Applications
2. For Fans/Pumps
3. For Applications Requiring High Starting Torque
Increasing the voltage of the V/f pattern increases motor torque, but
an excessive increase may cause motor overexcitation, motor over-
heating, or vibration.
Motor Specification: 60 Hz
(Factory setting)
Motor Specification: 50 Hz
n09
n10
n11
n12
n13
n14
n15
Constant
V
200
12
1.5
60 f
Setting
60.0
200.0
60.0
1.5
12
1.5
12
n09
n10
n11
n12
n13
n14
n15
Constant
V
200
12
1.3
50 f
Setting
50.0
200.0
50.0
1.3
12
1.3
12
Motor Specification: 60 Hz
Motor Specification: 50 Hz
10
n09
n10
n11
n12
n13
n14
n15
Constant
V
200
50
1.5
60
30
f
Setting
60.0
200.0
60.0
30.0
50
1.5
10
10
V
200
50
1.3
50
25
f
n09
n10
n11
n12
n13
n14
n15
Constant Setting
50.0
200.0
50.0
25.0
50
1.3
10
Motor Specification: 60 Hz
Motor Specification: 50 Hz
18
n09
n10
n11
n12
n13
n14
n15
Constant
V
200
24
1.5
60
3
f
Setting
60.0
200.0
60.0
3.0
24
1.5
18
18
V
200
24
1.3
50
2.5
f
n09
n10
n11
n12
n13
n14
n15
Constant Setting
50.0
200.0
50.0
2.5
24
1.3
18