81
Selects whether the “STOP” key on the digital operator is effective when operating the
inverter by an external source (input terminals or serial communications).
Operator stop key selection (n06)
Setting
Description
0
STOP key effective when running either from multi-function input terminals or communications.
When STOP key is pressed, the inverter stops according to the setting of parameter n04. At this
time, the digital operator displays “
” alarm (blinking). This stop command is held in the
inverter until both forward and reverse run commands are open, or until run command from
communications becomes zero.
1
STOP key is ineffective when running either from multi-function input terminals or
communications.