109
Protective
Operation
Output is shut
OFF and motor
coasts to a
stop.
EF
!
(External fault)
Inverter receives an external
fault input from control circuit
terminal.
EF0: External fault reference
through MEMOBUS
communications
EF2: External fault input
command from control
circuit terminal S2
EF3: External fault input
command from control
circuit terminal S3
EF4: External fault input
command from control
circuit terminal S4
EF5: External fault input
command from control
circuit terminal S5
Check the external
circuit (sequence).
CPF-00
Initial memory fault is
detected.
Cycle power.
If the fault remains,
replace the digital
operator or inverter.
CPF-01
ROM error is detected.
Cycle power. If the fault
remains, replace the
digital operator or
inverter.
CPF-04
EEPROM fault of inverter
control circuit is detected.
• Record all parameter
data and initialize the
parameters. (Refer
to page 25 for
parameter
initialization)
• Cycle power.
If the fault remains,
replace the inverter.
Alarm Display
Inverter
Status
Explanation
Causes and
Corrective Actions
Digital
Operator
RUN ALARM
(Green) (Red)
All manuals and user guides at all-guides.com
Summary of Contents for VS MINI J7 series
Page 13: ...13 2 IDENTIFYING THE PARTS All manuals and user guides at all guides com...
Page 14: ...14 Notes All manuals and user guides at all guides com...
Page 21: ...21 Standard Wiring All manuals and user guides at all guides com a l l g u i d e s c o m...
Page 23: ...23 Dimensions All manuals and user guides at all guides com...
Page 34: ...34 Notes All manuals and user guides at all guides com...
Page 38: ...38 Notes All manuals and user guides at all guides com...
Page 56: ...56 Notes All manuals and user guides at all guides com a l l g u i d e s c o m...
Page 98: ...98 Notes All manuals and user guides at all guides com...
Page 102: ...102 NOTES All manuals and user guides at all guides com...