Motor Overload Protection
Electronic thermal overload relay
Instantaneous Overcurrent
Motor coasts to a stop at approx. 200% of inverter rated
current
Overload
Motor coasts to a stop after 1 minute at 150% of inverter rated
output current
Overvoltage
Motor coasts to a stop if DC bus voltage exceed 410V
Undervoltage
Stops when DC bus voltage is approx. 200V or less (approx.
160V or less for single-phase series)
Momentary Power Loss
Following items are selectable: Not provided (stops if power
loss is 15ms or longer), continuous operation if power loss is
approx. 0.5s or shorter, continuous operation
Cooling Fin Overheat
Protected by electronic circuit
Stall Prevention Level
Individual levels during accel/running, enable/disable provided
during deceleration
Cooling Fan Fault
Protected by electronic circuit (fan stalling detection)
Ground Fault
Protected by electronic circuit (rated output current level)
O
the
r F
u
n
c
ti
ons
Power Charge Indication
RUN lamp stays ON or digital operator LED stays ON.
(Charge LED is provided for 400V)
ON until the DC bus voltage becomes 50V or less.
In
pu
t
S
ign
al
s
Multi-function Input
Four of the following input signals are selectable: Reverse run
(3-wire sequence), fault reset, external fault (NO/NC contact
input), multi-step speed operation, Jog command, accel/decel
time select, external baseblock (NO/NC contact input), speed
search command, accel/decel hold command, LOCAL/
REMOTE selection, communication/control circuit terminal
selection, emergency stop fault emergency stop alarm
Ou
tpu
t S
ign
a
ls
Multi-function Output
Following output signals are selectable (1 NO/NC contact
output):
Fault, running, zero speed, at frequency, frequency detection
(output frequency
≤
or
≥
set value), during over torque
detection, minor error, during baseblock, operation mode,
inverter run ready, during fault retry, during UV, during speed
search, during speed search, data output through
communication
Standard Functions
Full-range automatic torque boost, slip compensation, DC
injection braking current/time at start/stop frequency reference
bias/gain, [MEMOBUS communications (RS-485/422, max.
19.2K bps).]
Voltage Class
200V single- / 3-phase
Model
CIMR-J7AU
!!!!
3-phase
20P1
20P2
20P4
20P7
21P5
22P2
23P7
Single-phase
B0P1
B0P2
B0P4
B0P7
B1P5
-
-
All manuals and user guides at all-guides.com
all-guides.com
Summary of Contents for VS MINI J7 series
Page 13: ...13 2 IDENTIFYING THE PARTS All manuals and user guides at all guides com...
Page 14: ...14 Notes All manuals and user guides at all guides com...
Page 21: ...21 Standard Wiring All manuals and user guides at all guides com a l l g u i d e s c o m...
Page 23: ...23 Dimensions All manuals and user guides at all guides com...
Page 34: ...34 Notes All manuals and user guides at all guides com...
Page 38: ...38 Notes All manuals and user guides at all guides com...
Page 56: ...56 Notes All manuals and user guides at all guides com a l l g u i d e s c o m...
Page 98: ...98 Notes All manuals and user guides at all guides com...
Page 102: ...102 NOTES All manuals and user guides at all guides com...