n
If the 10A for the power section supply is no longer sufficient, you may use the power
module with the order number 007-1AB00. So you have also the possibility to define
isolated groups.
n
The power module with the order number 007-1AB10 is to be used if the 3A for the
electronic power supply at the backplane bus is no longer sufficient. Additionally you
get an isolated group for the DC 24V power section supply with max. 4A.
n
By placing the power module 007-1AB10 at the following backplane bus modules
may be placed with a sum current of max. 2A. Afterwards a power module is to be
placed again. To secure the power supply, the power modules may be mixed used.
(1) DC 24V for power section supply I/O area (max. 10A)
(2) DC 24V for electronic power supply bus coupler and I/O area
(3) DC 24V for power section supply I/O area (max. 4A)
(4) DC 24V for electronic power supply I/O area
Deployment of the power
modules
Power module 007-1AB00
Power module 007-1AB10
VIPA System SLIO
Basics and mounting
Wiring power modules
HB300 | FM | 050-1BS00 | en | 20-40
28