3.3 Technical data
Order no.
050-1BS00
Type
FM 050
Module ID
09C1 7800
Current consumption/power loss
Current consumption from backplane bus
85 mA
Power loss
1 W
Parallel switching of outputs for increased power
-
Status information, alarms, diagnostics
Status display
yes
Interrupts
yes, parameterizable
Process alarm
no
Diagnostic interrupt
yes, parameterizable
Diagnostic functions
yes, parameterizable
Diagnostics information read-out
possible
Module state
green LED
Module error display
red LED
Channel error display
none
Isolation
Between channels
-
Between channels of groups to
-
Between channels and backplane bus
ü
Between channels and power supply
-
Max. potential difference between circuits
-
Max. potential difference between inputs (Ucm)
-
Max. potential difference between Mana and Mintern
(Uiso)
-
Max. potential difference between inputs and Mana (Ucm)
-
Max. potential difference between inputs and Mintern
(Uiso)
-
Max. potential difference between Mintern and outputs
-
Insulation tested with
DC 500 V
Technical data SSI
Interfaces type
RS422
Encoder frequency / baud rate
parameterizable (125k, 250k, 500k, 1M, 1.5M, 2MHz)
SSI pause time
parameterizable (1, 2, 4, 8, 16, 32, 48, 64µs)
Normalization
parameterizable (0…15 Bit)
Bit length encoder data
parameterizable (8…32 Bit)
VIPA System SLIO
Hardware description
Technical data
HB300 | FM | 050-1BS00 | en | 20-40