SIEP C730600 86F MECHATROLINK-II Technical Manual
43
Code
Name
Causes
Possible Solutions
oFb02
Option Fault
An option of the same type is already installed in
option port CN5-A, CN5-B, or CN5-C.
Connect the option to the correct option port.
oFC00
Option Fault (CN5-B)
The option card installed into port CN5-C is not
compatible with the drive.
Connect the option to the correct option port.
•
Note: Use connector CN5-B when connecting DO-A3, AO-
A3, or two PG options. Use connector CN5-C when
connecting only one PG option.
To use other options, refer to those option manuals.
oFC02
Option Fault
An option of the same type is already installed in
option port CN5-A, CN5-B, or CN5-C.
Connect the option to the correct option port.
■
Minor Faults and Alarms
Code
Name
Causes
Possible Solutions
AEr
Station Address Setting Error
The node address for the option card is not in the
permitted setting range.
Set
F6-20
correctly.
CALL
Serial communication transmission
error
The communications cable wiring is incorrect.
•
Check for wiring errors.
•
Correct the wiring.
An existing short circuit or communications
disconnection
Check disconnected cables and short circuits and repair as needed.
Programming error on the master side
Check communications at start-up and correct programming
errors.
Communication circuitry is damaged.
•
Perform a self-diagnostics check
•
If the problem continues, replace either the control board or
the entire drive. For instructions on replacing the control
board, contact Yaskawa or a Yaskawa representative.
CyPo
Cycle Power to Active Parameters
Comm. Option Parameter Not Upgraded
Re-energize the drive to update the communication option
parameters.
Note:
If the option software version is not compatible or if you
install an incorrect option to the drive, it will trigger an alarm.
◆
Option Compatibility
Users may connect up to 3 options simultaneously depending on the type of option.
Note:
You can only connect one option to the GA500. Connect the option card to the CN5 connector.
Table 9.10 Option Compatibility
Option
Connector
Number of Cards Possible
PG-B3, PG-X3
CN5-B, C
2
PG-RT3
, PG-F3
CN5-C
1
DO-A3, AO-A3
CN5-A, B, C
1
SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3, SI-ES3, SI-
B3, SI-M3, SI-W3
, SI-EM3
, SI-EN3
, SI-EP3,
AI-A3
, DI-A3
CN5-A
1
*1
When connecting two PG option cards, use both CN5-B and CN5-C. When connecting only one PG option card, use the CN5-C
connector.
*2
Not available for the application with Motor 2 Selection.
*3
Not available with 1000-Series drive models with a capacities between 450 and 630 kW.
*4
When you use the input status of AI-A3 and DI-A3 as a monitor, you can connect AI-A3 and DI-A3 to CN5-A, CN5-B, or CN5-C.
10
European Standards
Figure 10.1 CE Mark
The CE mark indicates compliance with European safety and environmental regulations.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for
electronics manufacturers, and the EMC guidelines for controlling noise.
It is required for engaging in business and commerce in Europe.