Figure 7.3 Communication Phases
■
Phase 1: Initial status after power ON
Operation proceeds with a default transmission cycle of 2 ms. Operation proceeds with a default transmission
cycle of 2 ms. The transmission cycle is changed to the time indicated in the synchronous frame when a
CONNECT command is received from the master. Then the phase moves to phase 2 or phase 3 after a response to
the CONNECT command is returned.
Even if a transfer fault is detected in phase 1, no fault notification is provided.
■
Phase 2: Asynchronous communications
You can use all SI-T3 commands. Phase 2 starts to count the watchdog timer in the communications frame The
phase moves to phase 3 when a SYNC_SET command is received, and it moves to phase 1 when a
DISCONNECT command is received. If the drive receives the DISCONNECT command, the phase moves to
phase 1.
■
Phase 3: Synchronous communications
Watchdog timer faults in the communications frame are detected. The phase moves to phase 1 if the
DISCONNECT command is received. The phase moves to phase 2 if a reception fault or a watchdog timer fault is
detected.
◆
Application Layer Specifications
The data format for the application layer conforms to the MECHATROLINK-II command specifications for
standard inverter profile.
The SI-T3 option uses the main commands and sub-commands in the following tables.
Table 7.1 Main Command
Code
(Hex.)
Name
Function
00
NOP
No Operation
01
PRM_RD
Read Parameter
02
PRM_WR
Write Parameter
03
ID_RD
Read ID Number
04
CONFIG
RAM Write and EEPROM Write
05
ALM_RD
Read Alarm and Warning