![YASKAWA SI-EP3/V Technical Manual Download Page 43](http://html.mh-extra.com/html/yaskawa/si-ep3-v/si-ep3-v_technical-manual_907107043.webp)
9 Web Interface
43
YASKAWA
SIEP YEACOM 06 V1000 Option PROFINET SI-EP3/V Technical Manual
Table 28 Network Monitor Descriptions
Doc Links Tab
The Doc links tab contains links to the option documentation on the Yaskawa website.
Figure 27
Figure 27 Doc Links Tab View
Network Monitor
Explanation
Msg Tx OK
Cumulative number of messages transmit successfully from SI-EP3/V.
Msg Rx OK
Cumulative number of messages received successfully to SI-EP3/V.
Current Connections
Current number of open connections.
Control Connection Delta Time
The time between the last two writes to the Control register, MEMOBUS/Modbus address 0001H.
Msg Tx Dropped
Cumulative number of messages dropped due to output network buffer being full and unable to hold the new
message.
Msg Rx Dropped
Cumulative number of messages dropped due to input network buffer being full and unable to hold the new
message.
Collisions
Cumulative number of collisions (half duplex only) reported by the MAC/PHY (Media Access Control/
Physical Connection).
Msg Tx Errors
Cumulative number of transmit underruns and transmit stops reported by the
MAC/PHY.
Msg Rx Errors
Cumulative number of receive overruns, receive stops, and receive error frames reported by the MAC/PHY.
Tx Retry
Cumulative number of transmits in which the 1st attempt was delayed due to busy medium reported by the
MAC/PHY.
Note:
Cumulative counters are reset when the power supply is cycled.