7 PROFINET Messaging
25
YASKAWA
SIEP YEACOM 06 V1000 Option PROFINET SI-EP3/V Technical Manual
Table 9 Status Word for the PROFIdrive Communication Profile
Bit
Name
Value
STATE/Description
0 RDY_ON
1
READY TO SWITCH ON.
0
NOT READY TO SWITCH ON.
1 RDY_RUN
1 READY
TO
OPERATE.
0 OFF1
ACTIVE.
2 RDY_REF
1 ENABLE
OPERATION.
0 DISABLE
OPERATION.
3 TRIPPED
1 FAULT.
0 No
fault.
4 OFF_2_STA
1 OFF2
inactive.
0 OFF2
ACTIVE.
5 OFF_3_STA
1 OFF3
inactive.
0 OFF3
ACTIVE.
6 SWC_ON_INHIB
1 SWITCH-ON
INHIBIT
ACTIVE.
0
SWITCH-ON INHIBIT NOT ACTIVE.
7 ALARM
1 Warning/Alarm.
0 No
Warning/Alarm.
8
AT_SETPOINT
1
OPERATING. Actual value equals reference value (i.e., is within tolerance limits).
0
Actual value differs from reference value (i.e., is outside tolerance limits).
9 REMOTE
1
Drive control location: REMOTE.
0
Drive control location: LOCAL.
10 ABOVE_LIMIT
-
Not
supported.
11 to 15
-
-
Reserved