6 Related Parameters
YASKAWA ELECTRIC
TOBP C730600 82B YASKAWA AC Drive Option SI-P3 Installation Manual
35
F6-07
(3A8)
MultiStep Ref Priority
Select
0: MultiStep References Disabled
1: MultiStep References Enabled
Default: 0
Range: 0, 1
F6-08
(36A)
Comm Parameter Reset
@Initialize
Selects whether communication-related parameters
F6-
and F7-
are set back to original default
values when the drive is initialized using parameter
A1-03.
0: No Reset - Parameters retained
1: Reset - Back to factory default
Note: The setting value is not changed even when
F6-08 is set to 1 and the drive is initialized using
A1-03.
Default: 0
Range: 0, 1
F6-14
(3BB)
Communication Error Auto
Reset
Enables or disables the Communication Error Auto
Reset.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
F6-30
(3CB)
PROFIBUS-DP Node
Address
Sets the node address.
Default: 0
Min: 0
Max: 125
F6-31
(3CC)
PROFIBUS-DP Clear Mode
Selection
Selects the action to take after a “Clear Mode”
command is received.
0: Resets to 0
1: Maintains the previous value
Default: 0
Range: 0, 1
F6-32
(3CD)
PROFIBUS-DP Data
Format Selection
0: PPO Type
1: Conventional
2: PPO (bit0)
3: PPO Type (Enter)
4: Conv (Enter)
5: PPO (bit0, Enter)
Default: 0
Range: 0 to 5
F7-16
(3F4)
Timeout Value
Sets the time-out value for communication loss
detection in tenths of a second. A value of 0 disables
the connection time-out.
Example: An entered value of 100 represents 10.0
seconds.
Default: 0.0
Min: 0.0
Max: 30.0
F7-60
(780)
PZD1 Write
Sets MEMOBUS/Modbus address for PZD1 Write
(PPO Write).
The value of 0 to 2 enables the PZD1 Write as STW.
Default: 0H
Min: 0H
Max: FFFFH
F7-61
(781)
PZD2 Write
Sets MEMOBUS/Modbus address for PZD2 Write
(PPO Write).
The value of 0 to 2 enables the PZD2 Write as HSW.
Default: 0H
Min: 0H
Max: FFFFH
F7-62
(780)
PZD3 Write
Sets MEMOBUS/Modbus address for PZD3 Write
(PPO Write).
The value of 0 to 2 disables the PZD3 Write.
Default: 0H
Min: 0H
Max: FFFFH
F7-63
(783)
PZD4 Write
Sets MEMOBUS/Modbus address for PZD4 Write
(PPO Write).
The value of 0 to 2 disables the PZD4 Write.
Default: 0H
Min: 0H
Max: FFFFH
No.
(Addr. Hex)
Name
Description
Values