6 Related Parameters
YASKAWA ELECTRIC
TOBP C730600 82B YASKAWA AC Drive Option SI-P3 Installation Manual
37
F7-78
(792)
PZD9 Read
Sets MEMOBUS/Modbus address for PZD9 Read
(PPO Read).
The value of 0 to 2 disables the PZD9 Read.
Default: 0H
Min: 0H
Max: FFFFH
F7-79
(793)
PZD10 Read
Sets MEMOBUS/Modbus address for PZD10 Read
(PPO Read).
The value of 0 to 2 disables the PZD10 Read.
Default: 0H
Min: 0H
Max: FFFFH
<1> Set b1-02 = 3 to start and stop the drive with the PROFIBUS-DP master device using serial communications.
Set b1-01 = 3 to control the frequency reference of the drive via the master device.
<2> Setting this parameter to 3 will cause the drive to continue operation after detecting a fault. Take proper measures
such as installing an emergency stop switch when using setting 3.
<3> Settings 4 and 5 are not available on 1000-Series drives.
<4> Available in the A1000 software versions PRG: 1021 and later.
<5> Control method availability of this parameter depends on drive series.
1000-Series Drives: Parameter is available in CLV, AOLV/PM, and CLV/PM.
In AOLV/PM, this value is read as the Torque Limit.
GA700 Drives: Parameter is available in CLV, AOLV, AOLV/PM, and CLV/PM.
<6> Refer to the instruction manual of a specific drive to determine if settings 4 and 5 are available in the drive.
<7> The setting specifies that network communications provide the torque reference or torque limit. The motor could
rotate if the PLC does not supply a torque reference or torque limit.
<8> Available in the option software versions PRG: 2103 and later.
<9> All node addresses must be unique. Node addresses 0, 1, and 2 are typically reserved for control, maintenance,
and diagnostic equipment. The “Err” LED will illuminate when a value of 0 or a value greater than 125 is entered.
<10> Cycle power for setting changes to take effect.
<11> Requires also setting bit 0 to 1 to issue Run command. Refer to the option Technical Manual for more
information.
<12> When writing this parameter to the drive through the PROFIBUS-DP network, the parameter is validated by
automatically executing the Enter comma7nd.
No.
(Addr. Hex)
Name
Description
Values