6 Related Parameters
6
Related Parameters
set the drive for operation with the option. Confirm proper setting
of all parameters in
before starting network communications. Refer to the manual
packaged with the drive for details on setting parameters.
Table 8 Related Parameters
No.
(Addr. Hex)
Name
Description
Values
b1-01
(180)
Reference 1 Source
Selects the input method for frequency reference.
0: Keypad
1: Analog Input
2: Memobus/Modbus Communications
3: Option PCB
4: Pulse Train Input
Default: 1
Range: 0 to 4
(Set to 3)
b1-02
(181)
Run Command 1 Source
Selects the input method for the Run command.
0: Keypad
1: Digital Input
2: Memobus/Modbus Communications
3: Option PCB
Default: 1
Range: 0 to 3
(Set to 3)
d5-01
(29A)
Torque Control Selection
0: Speed Control
1: Torque Control
Default: 0
Range: 0, 1
F6-01
(3A2)
Communication Error
Selection
Selects drive response when a bUS error is detected
during communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast Stop (Use C1-09)
3: Alarm Only
4: Alarm - Run at d1-04
5: Alarm - Ramp to Stop
Default: 1
Range: 0 to 5
F6-02
(3A3)
Comm External Fault (EF0)
Detect
Selects the condition for external fault detection
(EF0).
0: Always detected
1: Detection during run only
Default: 0
Range: 0, 1
F6-03
(3A4)
Comm External Fault (EF0)
Select
Selects drive response for external fault input (EF0)
detection during option communications.
0: Ramp to Stop
1: Coast to Stop
2: Fast Stop (Use C1-09)
3: Alarm Only
Default: 1
Range: 0 to 3
F6-06
(3A7)
Torque Reference/Limit by
Comm
Enabling this parameter allows d5-01 to determine
whether the value is read as the Torque Limit value
(d5-01 = 0) or the Torque Reference value (d5-01 =
1).
0: Disabled
1: Enabled
Default: 0
Range: 0, 1