Drive Model
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp
Terminal
Model Number
Tool
Insulation Cap
Model No.
Code
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3
Machine No.
Die Jaw
4A0362
3/0 × 2P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080
100-051-558
4/0 × 2P
100-L12
TD-324,
TD-312
TP-100
100-051-560
250 × 2P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 2P
350 × 2P
180-L12
TD-327,
TD-314
TP-200
100-066-688
400 × 2P
200-L12
100-051-564
500
325-12
TD-328,
TD-315
TP-325
100-051-277
600
4A0414
4/0 × 2P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100
100-051-560
250 × 2P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 2P
4A0515
3/0 × 4P
3/0 × 4P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080
100-051-558
4/0 × 4P
4/0 × 4P
100-L12
TD-324,
TD-312
TP-100
100-051-560
250 × 4P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 2P
4A0675
4/0 × 4P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100
100-051-560
250 × 4P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 4P
4A0930
3/0 × 8P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080
100-051-558
4/0 × 8P
100-L12
TD-324,
TD-312
TP-100
100-051-560
250 × 8P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 8P
4A1200
4/0 × 8P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100
100-051-560
250 × 8P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 8P
Note:
Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
i.3 Electrical Installation Safety
34
YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions
Summary of Contents for P1000
Page 73: ......