Setting 2: IP20/NEMA Type 1 Enclosure
Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation b40 °C and
+50 °C requires output current derating.
Setting 3: External Heatsink Installation, Finless Drive
Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation b40 °C and
+50 °C requires output current derating.
100
85
70
55
0
L8-35 = 2: IP20/NEMA Type 1 Enclosure
L8-35 = 3: External Heatsink lnstallation
L8-35 = 0: IP00/Open-Chassis Enclosure
30
-10
40
50
Drive Rating
(%)
L8-12
(Ambient temp:
°
C)
L8-35 = 1: Side-by-Side Mounting
Figure i.29 Ambient Temperature and Installation Method Derating
u
Altitude Derating
The drive standard ratings are valid for installation altitudes up to 1000 m. For installations from 1000 m to 3000 m, the drive
rated voltage and the rated output current must be derated for 0.2% per 100 m.
u
Dimensions, Weight, Heat Loss
NOTICE
Refer to the
Mechanical Installation Chapter
and the
Specifications Chapter
of the
P1000 Technical Manual
SIEPYAIP1U01
which can be found on the CD-ROM packaged with the product.
i.9 European Standards
68
YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions
Summary of Contents for P1000
Page 73: ......