n
Three-Phase 600 V Class
Table i.7 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
Drive Model
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0003
5A0004
5A0006
R/L1, S/L2, T/L3
14
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖
,
⊕
1,
⊕
2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
5A0009
R/L1, S/L2, T/L3
14
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖
,
⊕
1,
⊕
2
–
14 to 10
B1, B2
–
14 to 10
10
12 to 10
5A0011
R/L1, S/L2, T/L3
10
14 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
14
14 to 6
⊖
,
⊕
1,
⊕
2
–
14 to 6
B1, B2
–
14 to 10
8
12 to 8
M5
2.0 to 2.5
(17.7 to 22.1)
5A0017
R/L1, S/L2, T/L3
10
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
10
10 to 6
⊖
,
⊕
1,
⊕
2
–
10 to 6
B1, B2
–
10 to 8
2.7 to 3.0
(23.9 to 26.6)
8
12 to 8
M6
5.4 to 6.0
(47.8 to 53.1)
5A0022
R/L1, S/L2, T/L3
8
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
10
10 to 6
⊖
,
⊕
1,
⊕
2
–
10 to 6
B1, B2
–
10 to 8
2.7 to 3.0
(23.9 to 26.6)
8
10 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
5A0027
5A0032
R/L1, S/L2, T/L3
6
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2, W/T3
6
6 to 4
⊖
,
⊕
1,
⊕
2
–
6 to 4
B1, B2
–
10 to 8
M5
2.7 to 3.0
(23.9 to 26.6)
6
10 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
5A0041
R/L1, S/L2, T/L3
6
10 to 3
M8
9.0 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
6
10 to 3
⊖
,
⊕
1
–
6 to 1
B1, B2
–
12 to 3
6
6
5A0052
R/L1, S/L2, T/L3
4
10 to 3
M8
9.0 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
6
10 to 3
⊖
,
⊕
1
–
6 to 1
B1, B2
–
8 to 3
6
6
i.3 Electrical Installation Safety
YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions
29
Summary of Contents for P1000
Page 73: ......