Ladder Software Setting (for MPE720 Ver.6)
1
Start the ladder software.
2
Make a project file.
3
From the tree view, double-click [Module Configuration].
[Engineering Manager] starts.
4
In the [Engineering Manager]’s [Controller], use the pull-down menu to select the rack classification and
communication module.
Set the number associated with the slot number used by the communication module.
When you select the communication module, its setting information is displayed in the [Engineering Manager]’s
[Module details].
5
In the in [Module details], double-click the No. field’s numeric portion.
Double-click the number associated with the slot number connected to the Ethernet unit.
6
Save the settings and exit [Engineering Manager].
7
After turning ON the communication module’s "INIT" DIP Switch, turn ON the power supply.
8
Write the settings to the communication module.
9
Turn OFF the External Device’s power supply, turn OFF the "INIT" DIP Switch, and turn the External Device’s
power back ON.
Notes
•
Check with a network administrator about IP address. Do not set the duplicate IP address.
Setup Items
Setup Description
Transmission parameter
This Station IP address
PLC IP address
• Please make the connection parameter blank.
Communication is not possible when a connection parameter is set.
• To write the settings, select the [Save to flash after transferring to the controller] check
box.
If the data is transferred without selecting the check box, the transferred data is
deleted when restarting the External Device.