Register No.
Contents
000FH
Control Selection Setting
bit 0
Reserved
bit 1
PID Setpoint Input
bit 2, 3
Reserved
bit 4
PI2 Target Input
bit 5 to B
Reserved
bit C
Enable Terminal S5 Input for Broadcast Data
bit D
Enable Terminal S6 Input for Broadcast Data
bit E
Enable Terminal S7 Input for Broadcast Data
bit F
Enable Terminal S8 Input for Broadcast Data
0010H to 001AH
Reserved
001BH
Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)
001CH
Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 H)
001DH to 001FH
Reserved
3004H
Set Time – Hours/Minutes (HHmm)
3005H
Set Date – Year/Day of Week (YYdd)
3006H
Set Date – Month/Day (MMDD)
3007H
RTC Set Command/Statud
0 = Complete
1 = Set RTC data using registers 3004H to 3006H
8 = failed
302FH
RTC Enter
0 = Overwrite RTC data using registers 3004H to 3006H. Only effective when 3030H bit 1 (RTC Enter Enable) is set.
3030H
bit 1
RTC Enter Enable
bit 2
RTC TIE Fault Enable
C.9 MEMOBUS/Modbus Data Table
466
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual