B.12 P: Pump Parameters
u
P1: Pump Basic
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
P1-01
(0C00) Pump Mode
Pump Mode
0: Drive Only
1: Contactor Lag
3: Memobus Network
0: Drive only
1: Contactor lag
3: MEMOBUS network
Default: 0
Range: 0, 1, 3
P1-02
(0C01) System Units
System Units
0: No Unit
1: PSI :lb/SqrInch
2: Pa:Pascals
3: Bar:Bar
4: "WC:InchOfWater
5: "Hg:Inch Mercury
6: ft: feet
7: m: meters
8:
°
F:DegFarenheit
9:
°
C:DegCelsius
10: %: Percent
11: kPA: kilopascal
25: Flow (use P6-04)
26:
Custom(P1-32~34)
0: No unit
1: PSI: Pounds per square inch
2: Pa: Pascals
3: Bar: Bar
4: ”WC: Inch of water
5: ”Hg: Inch of Mercury
6: ft: feet
7: m: meters
8:
°
F: Degrees Fahrenheit
9:
°
C: Degrees Celsius
10: Percent
11: kPA: kilopascal
25: Flow (Use P6-04)
26: Custom units
Default: 1
Range: 0 to 11;
25, 26
P1-03
(0C02)
Feedback Device
Scaling
FB Dev. Scaling
Sets the scaling of feedback device in user-set units.
Default: 145.0
PSI
Min.: 0.1
Max.: 6000.0
P1-04
(0C03) Start / Draw Down
Level
Start-DrawDn Lvl
The system starts when the feedback level drops below the start
level for the time set in P1-05. This level also specifies the wake-
up level when the drive is in Sleep Mode.
When this parameter is set to a negative value, the feedback level
must drop that amount below the setpoint.
Setting this parameter to 0.0 disables the function. When P1-01,
Pump Mode, is set to 3 (MEMOBUS network), this function is
active only on the first drive in the network.
Note:
When PID operates in reverse mode, the system
will start when the feedback has risen above the
start level for the time set to P1-05.
Min.: 0.0
Max.: 999.9
P1-05
(0C02) Start Level Delay Time S-Lev Delay Time
The system starts when the feedback level drops below the start
level for the time set in this parameter.
Default: 1 s
Min.: 0
Max.: 3600
P1-06
(0C05) Minimum Pump Speed Min. Pump Speed
Minimum frequency at which the drive will run. Applies to both
HAND and Automatic modes.
Note:
For minimum pump frequency, the drive will use
the highest setting from among P1-06, P4-12
(Thrust Bearing Frequency), or d2-02 (Reference
Lower Limit).
Min.: 0.0
Max.: [E1-04]
P1-07
(0C06)
Minimum Pump Speed
Units
MinPumpSpdUnits
0: Hz
1: RPM
Sets the units and decimal place for parameter P1-06.
0: Hz
1: RPM
Note:
Changing this parameter will reset the P1-06
default value.
Default: 0
Range: 0, 1
–
P1-08
(0C07) Low Feedback Level
Low FB Level
Sets the lower detection level for the PID feedback.
Min.: 0.0
Max.: 999.9
B.12 P: Pump Parameters
402