HOA Keypad Display
Minor Fault Name
oH5
Motor Overheat (NTC Input)
The motor temperature exceeded the level set to L1-16 (or L1-18 for motor 2)
Cause
Possible Solutions
Motor has overheated.
• Reduce the load.
• Check the ambient temperature.
<1> Detected in models 4A0930 and 4A1200.
HOA Keypad Display
Minor Fault Name
oL1
Motor Overload
The electronic motor overload protection tripped
Cause
Possible Solution
Load is too heavy
Reduce the load.
Cycle times are too short during
acceleration and deceleration
Increase the acceleration and deceleration times (C1-01 through C1-04).
A general-purpose motor is driven below
the rated speed with a high load
• Reduce the load.
• Increase the speed.
• If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor
specifically designed to operate in the desired speed range.
The output voltage is too high
• Adjust the user-set V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
The wrong motor rated current is set to
E2-01
• Check the motor-rated current.
• Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
The base frequency is set incorrectly
• Check the rated frequency indicated on the motor nameplate.
• Enter the rated frequency to E1-06 (Base Frequency).
The electrical thermal protection
characteristics and motor overload
characteristics do not match
• Check the motor characteristics.
• Correct the type of motor protection that has been selected (L1-01).
• Install an external thermal relay.
The electrical thermal relay is operating at
the wrong level
• Check the current rating listed on the motor nameplate.
• Check the value set for the motor rated current (E2-01).
Motor overheated by overexcitation
operation
• Overexcitation increases the motor loss and the motor temperature. Excessive duration of overexcitation
may cause motor damage. Prevent excessive overexcitation operation or apply proper cooling to the motor.
• Reduce the excitation deceleration gain (n3-13).
• Set L3-04 (Stall Prevention during Deceleration) to a value other than 4.
Parameters related to Speed Search are set
incorrectly
• Check values set to Speed Search related parameters.
• Adjust the Speed Search current and Speed Search deceleration times (b3-02 and b3-03 respectively).
• After Auto-Tuning, set b3-24 to 1 to enable Speed Estimation Speed Search.
Output current fluctuation due to power
supply loss
Check the power supply for phase loss.
HOA Keypad Display
Minor Fault Name
oL2
Drive Overload
The thermal sensor of the drive triggered overload protection.
Cause
Possible Solution
Load is too heavy
Reduce the load.
Acceleration or deceleration time is too
short
Increase the settings for the acceleration and deceleration times (C1-01 through C1-04).
The output voltage is too high
• Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not lower E1-08 and E1-10 excessively. This reduces load tolerance at low speeds.
Drive capacity is too small
Replace the drive with a larger model.
Overload occurred when operating at low
speeds
• Reduce the load when operating at low speeds.
• Replace the drive with a model that is one frame size larger.
• Lower the carrier frequency (C6-02).
Excessive torque compensation
Reduce the torque compensation gain in parameter C4-01 until there is less current but no speed loss.
5.3 Alarm Detection
280
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual