No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U1-92
(0BA7) Pump Status
Pump Status
Displays Pump Running Status.
U1 - 92=
00000000
Drive
Pump 2
Pump 3
Pump 4
Pump 5
Pump 6
Not used
Not used
1
1
1
1
1
1
0
0
No signal output
available
–
U1-93
(0BA8)
Total Setpoint
Compensation
Total SP Comp.
Displays the total absolute Setpoint Compensation.
No signal output
available
dep. on
P1-02
U1-94
(0BA9) Motor Speed
Motor Speed
Displays the absolute value of the output frequency (U1-02)
converted to RPM.
No signal output
available
1 RPM
U1-96
(0BAB)
PI Auxiliary Control
Feedback Level
PI Aux FB Level
Displays the PI Auxiliary Control Feedback Level (H3-
oo
=
27).
N/A
Unit
dep. on
Q6-21
Res.
dep. on
Q6-22
U1-97
(0BAC) Water Level
Water Level
Displays the amount of water above the water level sensor.
Full scale:
10 V = Q4-02
0.1 ft.
U1-98
(0BAD) Suction Pressure
Suction Pressure
Displays the amount of suction pressure.
Full scale:
10 V = Q5-02
0.1 PSI
or ”Hg
U1-99
(0BAE)
Anti-No-Flow Timer
ANF Timer
The Anti-No-Flow reduces the output frequency when this
value reaches the P2-24 setting.
No signal output
available
0.1 s
<1> Display is in the following units:
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> The display resolution depends on the ND selection. This value has two decimal places (0.01 kW) if the drive is set for a maximum applicable
<5> Available in drive software versions PRG: 8551 and later.
<6> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
<7> Monitor is available through the Quick Monitor screen.
u
U2: Fault Trace
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U2-01
(0080)
Current Fault
Current Fault
Displays the current fault.
No signal output
available
–
U2-02
(0081)
Previous Fault
Last Fault
Displays the previous fault.
No signal output
available
–
U2-03
(0082)
Frequency Reference at
Previous Fault
Frequency Ref
Displays the frequency reference at the previous fault.
No signal output
available
0.01 Hz
U2-04
(0083)
Output Frequency at
Previous Fault
Output Freq
Displays the output frequency at the previous fault.
No signal output
available
0.01 Hz
U2-05
(0084)
Output Current at
Previous Fault
Output Current
Displays the output current at the previous fault.
Note:
The unit is expressed in 1 A for models 4A0930
and 4A1200.
No signal output
available
B.16 U: Monitors
440
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual