3.8 Control Circuit Wiring
YASKAWA ELECTRIC
TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
77
El
ec
tr
ical
I
n
st
al
lat
ion
3
■
Ferrule-Type Wire Terminals
Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire
ends with insulated sleeves before connecting to the converter. See
for dimensions.
Figure 3.37
Figure 3.34 Ferrule Dimensions
Table 3.12 Ferrule Terminal Types and Sizes
◆
Wiring the Control Circuit Terminal
This section describes the proper procedures and preparations for wiring the control terminals.
WARNING!
Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could
result in death or serious injury.
NOTICE:
Separate control circuit wiring from main circuit wiring (terminals R/ 1, S/ 2, T/ 3, r1/ 11, 1/ 21, t1/ 31, –, +) and other
high-power lines. Improper wiring practices could result in converter malfunction due to electrical interference.
NOTICE:
Separate wiring for digital output terminals MA, MB, MC, M1 to M6 from wiring to other control circuit lines. Improper wiring
practices could result in converter or equipment malfunction or nuisance trips.
NOTICE:
Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral
devices could result in converter performance degradation due to improper power supply.
NOTICE:
Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices
could result in converter or equipment malfunction due to short circuit.
NOTICE:
Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in
converter or equipment malfunction or nuisance trips.
Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete.
Prepare the ends of the control circuit wiring as shown in
. Refer to
for the treatment of the ends
of the shield wire.
NOTICE:
Do not tighten screws beyond the specified tightening torque. Failure to comply may result in erroneous operation, damage
to the terminal block, or cause a fire.
NOTICE:
Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in converter
or equipment malfunction due to electrical interference.
Size
mm
2
(AWG)
Type
L
(mm)
d1
(mm)
d2
(mm)
Manufacturer
0.25 (24)
AI 0.25–6YE
10.5
0.8
2
PHOENIX CONTACT
0.34 (22)
AI 0.34–6TQ
10.5
0.8
2
0.5 (20)
AI 0.5–6WH
14
1.1
2.5
φ
d1
φ
d2
6 mm
L