3.8 Control Circuit Wiring
78
YASKAWA ELECTRIC
TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
Connect control wires as shown in
.
Figure 3.38
Figure 3.35 Terminal Board Wiring Guide
Figure 3.39
Figure 3.36 Terminal Board Location Inside the Converter
For the control circuit wires, use shielded twisted-pair wires that have been prepared as shown in
.
Figure 3.40
Figure 3.37 Preparing the Ends of Shielded Cables
NOTICE:
The analog signal wiring between the converter and the operator station or peripheral equipment should not exceed 50
meters when using an analog signal from a remote source. Failure to comply could result in poor system performance.
A – Loosen screw to insert wire.
C – Avoid fraying wire strands when
stripping insulation from wire.
Strip length 5.5 mm.
B – Single wire or stranded wire
D – Blade depth of 0.4 mm or less
E – Blade width of 2.5 mm or less
A – Converter side
D – Shield sheath (insulate with tape)
B – Insulation
E – Shield
C – Control device side
A
B
C
D
Preparing wire
terminal ends
YAI
YAI
A
E
B
C
D