Model
Terminal
Recomm. Gauge
mm
2
Applicable Gauge
(IP20 Applicable
Gauge
)
mm
2
Wire Stripping
Length
mm
Terminal Screw
Tightening
Torque
N
∙
m (lbf
∙
in)
Size
Shape
2415
R/L1, S/L2, T/L3
120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
Hex self-locking nut
35
(310)
U/T1, V/T2, W/T3
120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
Hex self-locking nut
35
(310)
-, +1
120 × 2P
95 - 185 × 2P
(185 × 2P)
-
M12
Hex self-locking nut
35
(310)
+3
70 × 2P
50 - 95 × 2P
(-)
-
M12
Hex self-locking nut
35
(310)
120
120 - 240
(-)
-
M12
Hex bolt (slotted)
32 - 40
(283 - 354)
*1
For IP20 protection, use wires that are in the range of applicable gauges.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
For wire gauges more than 30 mm
2
, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 lbf∙in to 40 lbf∙in).
*4
Install an ELCB with this wire gauge to maintain compliance with IEC/EN 61800-5-1:2007.
*5
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*6
A junction terminal is necessary to connect a braking unit (CDBR-series) to terminals - and +3.
Three-Phase 400 V Class
Table 4.3 Main Circuit Wire Gauges and Tightening Torques (400 V Class)
Model
Terminal
Recomm. Gauge
mm
2
Applicable Gauge
(IP20 Applicable
Gauge
)
mm
2
Wire Stripping
Length
mm
Terminal Screw
Tightening
Torque
N
∙
m (lbf
∙
in)
Size
Shape
4002
R/L1, S/L2, T/L3
2.5
2.5 - 10
(2.5 - 10)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
2.5
2.5 - 10
(2.5 - 10)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
-, +1, +2
2.5
2.5 - 16
(2.5 - 16)
18
M5
Slotted (-)
2.3 - 2.5
(19.8 - 22)
B1, B2
2.5
2.5 - 4
(2.5 - 4)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
2.5
2.5 - 10
(-)
-
M4
Phillips/slotted
combo
1.2 - 1.5
(10.6 - 13.3)
4003
R/L1, S/L2, T/L3
2.5
2.5 - 10
(2.5 - 10)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
2.5
2.5 - 10
(2.5 - 10)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
-, +1, +2
2.5
2.5 - 16
(2.5 - 16)
18
M5
Slotted (-)
2.3 - 2.5
(19.8 - 22)
B1, B2
2.5
2.5 - 4
(2.5 - 4)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
2.5
2.5 - 10
(-)
-
M4
Phillips/slotted
combo
1.2 - 1.5
(10.6 - 13.3)
4005
R/L1, S/L2, T/L3
2.5
2.5 - 10
(2.5 - 10)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
2.5
2.5 - 10
(2.5 - 10)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
-, +1, +2
2.5
2.5 - 16
(2.5 - 16)
18
M5
Slotted (-)
2.3 - 2.5
(19.8 - 22)
B1, B2
2.5
2.5 - 4
(2.5 - 4)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
2.5
2.5 - 10
(-)
-
M4
Phillips/slotted
combo
1.2 - 1.5
(10.6 - 13.3)
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...