d3-01
Jump
Frequency 1
d3-01 to d3-04 allow programming of three
prohibited frequency reference points for eliminating
problems with resonant vibration of the motor/
machine. This feature does not eliminate the selected
frequency values, but accelerates and decelerates the
motor through the prohibited bandwidth.
The parameters must be according to the rule
d3-01 ≥ d3-02 .
0.0 to
400.0
0.0
Hz
O
294
–
d3-02
Jump
Frequency 2
0.0
Hz
O
295
–
d3-04
Jump
Frequency
Width
This parameter sets the dead-band width around each
selected prohibited frequency reference point. The
bandwidth becomes the designated Jump frequency,
plus or minus d3-04.
0.0 to
20.0
1.0
Hz
O
297
–
d4: Frequency Reference Hold
Use d4 parameters to configure the drive frequency reference hold function.
d4-01
Frequency
Reference
Hold Function
Selection
Determines if the frequency reference or frequency
reference bias is saved when the Run command is
removed or the power goes off.
0: Disabled
1: Enabled
This parameter is effective when the multi-function
inputs “Accel/Decel Ramp Hold” or “Up/Down”
commands are selected (H1-
oo
= A or 10/11).
0, 1
0
O
298
–
<1>
Parameter can be changed during run.
<2>
B.2 Parameter Table
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual
229