n
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL
approval requires the use of UL Listed closed-loop crimp terminals when wiring the drive
main circuit terminals. Use only the tools recommended by the terminal manufacturer for
crimping. The wire gauges listed in
are Yaskawa
recommendations. Refer to local codes for proper wire gauge selections.
Table C.7 Wire Gauge and Torque Specifications
Drive
Model
Terminal
For Japan and Asia
For United States
For Europe and China
Screw
Size
Tightening
Torque
N•m (lb.in.)
Recomm.
Gauge
mm
2
Wire Range
mm
2
Recomm.
Gauge
AWG,
kcmil
Wire Range
AWG, kcmil
Recomm.
Gauge
mm
2
Wire Range
mm
2
BA0001
BA0002
BA0003
R/L1, S/L2,
T/L3
2
0.75 to 2
14
18 to 14
2.5
0.75 to 2.5
M3.5
0.8 to 1.0
(7.1 to 8.9)
U/T1, V/T2,
W/T3
2
0.75 to 2
14
18 to 14
2.5
0.75 to 2.5
⊖
,
⊕
1,
⊕
2
2
0.75 to 2
–
18 to 14
–
0.75 to 2.5
B1, B2
2
0.75 to 2
–
18 to 14
–
0.75 to 2.5
2
0.75 to 2
14
18 to 14
2.5
0.75 to 2.5
BA0006
R/L1, S/L2,
T/L3
2
2 to 5.5
12
14 to 10
2.5
2.5 to 6
M4
1.2 to 1.5
(10.6 to
13.3)
U/T1, V/T2,
W/T3
2
2 to 5.5
14
14 to 10
2.5
2.5 to 6
⊖
,
⊕
1,
⊕
2
2
2 to 5.5
–
14 to 10
–
2.5 to 6
B1, B2
2
2 to 5.5
–
14 to 10
–
2.5 to 6
3.5
2 to 5.5
10
14 to 10
2.5
2.5 to 6
BA0010
R/L1, S/L2,
T/L3
3.5
2 to 5.5
10
14 to 10
2.5
2.5 to 6
M4
1.2 to 1.5
(10.6 to
13.3)
U/T1, V/T2,
W/T3
2
2 to 5.5
14
14 to 10
2.5
2.5 to 6
⊖
,
⊕
1,
⊕
2
3.5
2 to 5.5
–
14 to 10
–
2.5 to 6
B1, B2
2
2 to 5.5
–
14 to 10
–
2.5 to 6
3.5
2 to 5.5
10
14 to 10
2.5
2.5 to 6
<1>
Gauges listed here are for use in Japan and Asia.
<2>
Gauges listed here are for use in the United States.
<3>
Gauges listed here are for use in Europe and China.
C.3 UL Standards
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual
265
C
Standards Compliance