u
Changing Parameter Settings or Values
This example explains changing C1-01 (Acceleration Time 1) from 10.0 seconds (default) to
20.0 seconds.
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
2.
Press the
key until the Setup Mode Screen appears.
3.
Press the
key to view the parameter setting display.
4.
Scroll through parameters by pressing the
key until C1-01
appears.
5.
Press
to view the current setting value (10.0). (Number
farthest to the left flashes)
6.
Press
until the desired number is selected. (“1” flashes)
7.
Press the
key and enter 0020.0.
8.
Press
and the drive will confirm the change.
9.
The display automatically returns to the screen shown in Step 4.
10.
Press the
key until back at the initial display.
u
Verifying Parameter Changes: Verify Menu
The Verify Menu lists edited parameters from the Programming Mode. The Verify Menu
helps determine which settings have been changed, and is particularly useful when replacing
a drive. If no settings have been changed the Verify Menu will read
. The Verify menu
also allows users to access and re-edit edited parameters.
Note:
The Verify Menu will not display parameters from the A1 group even if those parameters have been
changed from default settings.
The following example is a continuation of the steps beginning on page
C1-01 is accessed using the Verify Menu and is changed again to 20.0 s.
To check the list of edited parameters:
4.3 The Drive and Programming Modes
90
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual