8 CC-Link Data Table
YASKAWA ELECTRIC
TOBP C730600 83C YASKAWA AC Drive Option SI-C3 Installation Manual
43
Energy-Saving Unit
→
PLC
Table 12 Remote I/O Table (Energy-Saving Unit
→
PLC)
Device
Name
Description
Default
RX0
During Run/During Stop
ON: During Run, OFF: During
Stop
–
RX1
During Regeneration
ON: During Regeneration
–
RX2
Terminals M1-M2 Function Multi-function output: H2-01
H2-01 = 25: During
Run 1
RX3
During Run (Converter
Ready)
–
–
RX4
Reserved
–
–
RX5
Undervoltage (Uv)
–
–
RX6
Terminals P1-PC
Function
<1>
Multi-function output: H2-02
H2-02 = 26: During MC ON
RX7
Terminals P2-PC
Function
<1>
Multi-function output: H2-03
H2-03 = 6: Energy-Saving Unit
Ready
RX8
Momentary Power Loss
Ride-Thru/Recovery from
Momentary Power Loss
–
–
RX9
ComCtrlstatus/NetCtrlstatus
–
–
RXA
CC-Link Option Fault
Communication error between
energy-saving unit and CC-Link
device
–
RXB
During Active Current Limit
–
–
RXC
Obtain Monitor Data
ON: Monitor data has been
updated.
–
RXD
Alarm
–
–
RXE
Fault
–
–
RXF
Command Code Execute
Complete
ON: Displayed after the specified
command code has been executed.
RXF signal switches off when the
RYF command is no longer
present.
–
RX10
During Reset Signal Input
–
–
RX11
oPE Error
–
–
RX12
Power Supply Undervoltage
(AUv)
–
–
RX13
to 19
Reserved
–
–
RX1A
Error
ON: Fault occurred on the
energy-saving unit side.
–
TOBP_C730600_83C_3_0_E.fm 43 ページ 2018年10月24日 水曜日 午後5時59分