8 CC-Link Data Table
YASKAWA ELECTRIC
TOBP C730600 83C YASKAWA AC Drive Option SI-C3 Installation Manual
41
Note:
If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the
register. Using RYE (Frequency Reference 2 flag) too often can shorten the performance life of
the drive's internal memory.
n
Energy-Saving Unit Remote I/O
PLC
→
Energy-Saving Unit
Table 11 Remote I/O Table (PLC
→
Energy-Saving Unit)
RXD
Frequency Setting Ready 1
ON: Displays the main frequency
reference that has been set.
–
RXE
Frequency Setting Ready 2
ON: Displays the data set to d1-01
(Frequency Reference 1).
Also sets the main frequency
reference at the same time.
–
RXF
Command Code Execute
Complete
ON: Displayed after the specified
command code has been executed.
RXF signal switches off when the
RYF command is no longer
present.
–
RX10
to 19
Reserved
–
–
RX1A
Error
ON: Fault occurred on the drive
side.
–
RX1B
Remote Station Ready
ON: Drive is ready to operate.
–
RX1C
to 1F
Reserved
–
–
<1> Terminals will differ depending on the model of the drive. Refer to
Terminals that Change depending on the
Model of the Drive on page 46
for information on terminals.
Device
Name
Description
Default
RY0
Run Command/Automatic
Run Command
ON: Run Command/Automatic
Run Command,
OFF: Stop Command
–
RY1
Forced Run Command
ON: Forced Run Command,
OFF: Stop
–
RY2
Terminal S3 Function
Multi-Function Input: H1-03
H1-03 = 24: External Fault
RY3
Terminal S4 Function
Multi-Function Input: H1-04
H1-04 = 14: Fault Reset
RY4
Terminal S5 Function
Multi-Function Input: H1-05
H1-05 = F: Through Mode
RY5
Terminal S6 Function
Multi-Function Input: H1-06
H1-06 = F: Through Mode
RY6
Terminal S7 Function
Multi-Function Input: H1-07
H1-07 = F: Through Mode
RY7
Terminal S8 Function
Multi-Function Input: H1-08
H1-08 = 8: Baseblock command
(N.O.)
RY8
Reserved
–
–
Device
Signal Name
Description
Default