8 CC-Link Data Table
42
YASKAWA ELECTRIC
TOBP C730600 83C YASKAWA AC Drive Option SI-C3 Installation Manual
Note:
Although RYF is triggered by the rising edge of the signal, they are otherwise enabled depending
on the value that is input.
RY9
External Baseblock
Command
ON: Motor coasts to stop.
OFF: Energy-saving unit will
begin operating as soon as a Run
command is given.
–
RYA
External Fault
ON: External Fault Input (EF0)
–
RYB
Reserved
–
–
RYC
Monitor Reference
ON: Monitor data specified in the
monitor code is set to remote
register RW
R0
.
When switching between monitors
using RYC (Monitor Reference),
RYC needs to be turned off and
then back on again after the
monitor code has been changed.
RYD, E
Reserved
–
–
RYF
Command Code Execute
Request
Request to execute the command
code.
Triggered by the rising edge of the
signal.
RY10
Terminals M1-M2 Function
Multi-Function Relay Output 1
(terminal M1-M2)
–
RY11
Terminals P1-PC
Function
<1>
Multi-Function Photocoupler
Relay Output 1 (terminal P1-PC)
–
RY12
Terminals P2-PC
Function
<1>
Multi-Function Photocoupler
Relay Output 2 (terminal P2-PC)
–
RY13
Reserved
–
–
RY14
Terminal S1 Function
Multi-Function Input: H1-01
Function is disabled when for the
Run Command (H1-01 = 4B).
RY15
Terminal S2 Function
Multi-Function Input: H1-02
Function is disabled when for the
Stop Command (H1-02 = 4C).
RY16
RY17 Enabled/Disabled
Selection
–
–
RY17
Terminal MA/MB-MC
Function
Fault Contact Output (terminal
MA/MB-MC)
–
RY18, 19
Reserved
–
–
RY1A
Fault Reset
Resets an energy-saving unit fault.
–
RY1B
to 1F
Reserved
–
–
<1> Terminals will differ depending on the model of the drive. Refer to
Terminals that Change depending on the
Model of the Drive on page 46
for information on terminals.