67
1100 1100 suBMenu setup
1110
1110 FACTORY SET
Restores the HV to factory setting
USA
Possible settings:
EUROPE, USA
To restore the HYDROVAR to factory settings select Europe or USA.
For reset press button until “DONE” appears.
1120
1120 PASSWORD 2
Enter password by pressing
▲
or
▼
0000
The below mentioned parameters are available after entering the correct password!
For more information, contact your local distributor!
1125
1125 CLR ERRORS
Clear error memory of selected unit
UNIT X
or on ALL units (Cascade Serial/Synchron)
Possible settings:
1 – 8, ALL
To clear the error memory either (1-8) for one specific unit or ALL for all units, can be selected.
For reset press button till “RESET” appears.
1130
1130 CLR MOTORH.
Clear motor hours for selected unit
UNIT X
or on ALL units (Cascade Serial/Synchron)
Possible settings:
1 – 8, ALL
Set desired unit where the Motor Hours should be cleared (or ALL) and press button until “RESET”
appears.
1135
1135 CLR OPERAT.
Clear operation time
Press 3 sec.
The operation time indicates the total time the HYDROVAR is already connected to power supply. For reset
the operation time of the current HYDROVAR press button till “RESET” appears.
1200
1200 suBMenu
rs485-interFace
user interface
The following 3 Parameters are necessary for communication between the HYDROVAR and an external
device (e.g. PLC) via standardized Modbus-protocol. Set desired address, Baudrate and Format according
to the system requirements.
1205
1205 ADDRESS
Set desired address for the user interface
1
Possible settings:
1 - 247
proGraMMinG