22 SELECT DEVICE
Select device
* 1 *
Possible settings:
1-8
Check the current status, the motor hours and the most recent failures of any given drive. The drive selec-
tion is determined by the current selected mode [105]. Select desired unit by pressing
▲
or
▼
.
cascade serial/sYncHron:
The selection specifies the address of the HYDROVAR units
E.g. Device 1 -> Master Inverter with pre-selected address 1
Device 2 -> Basic Inverter with pre-selected address 2
Device 3 -> Basic Inverter with pre-selected address 3
To set the address on a Basic Inverter, see chapter addressing.
To set the address on a Master Inverter, see parameter [106] or submenu [1200] RS485-Interface.
Mode cascade relaY:
device
enabled By
1
Master Inverter
2
fixed speed pump
Relay 1
X10: 1
3
fixed speed pump
Relay 2
X10: 2
4
fixed speed pump
Relay 3
X10: 3
5
fixed speed pump
Relay 4
X10: 4
6
fixed speed pump
Relay 5
X10: 5
7
not used
8
not used
23
23 STATUS DEVICE
Status of the selected device
Stopped
Possible messages: Running, Stopped, Disabled, OFF, Preparing
(Mode Casc. Serial/Synchr)
relay on, relay off
(Mode: Cascade Relay)
Solorun, Faulted
(all Modes)
Shows the status of the device
Mode cascade relaY:
relay_on
->
Relay contact is closed -> fixed-speed-pump is running
relay_off
->
Relay contact is opened -> fixed-speed-pump is stopped
Mode cascade serial/sYncHron:
running
->
Pump is running
stopped
->
Pump is stopped
disabled
->
Pump is disabled by an external input.
(Stopped with buttons or disabled with parameter ENABLE DEVICE [24]) or by external
on/off contact open
preparing ->
A new unit is connected to the multi-pump system and Data is being transferred
solo run
->
Solorun (Hand Mode) is activated (XSL closed)
faulted
->
A failure has occurred on the current unit