Xylem Goulds J Series Instruction Manual Download Page 6

6

All other horizontal deep well jet pumps, ¾

  

hp and 

larger, should use an AV22KIT, or an AV22 and a JDW 

tubing kit. The AV22 has a tapping to which you connect 

the new, longer pressure switch tubing. This allows the 

pressure switch to read the pressure on the outboard 

side of the valve rather than in the pump casing. Remove 

the straight or elbow compression fitting from the pump 

casing. Use the pipe plug in the JDW or AV22KIT to plug 

the hole in the pump casing. Remove the fitting from 

the pressure switch. Cut the old tubing in half and slide 

the compression fittings off the old tubing. Note that the 

fitting will only slide in one direction. You can now reuse 

the elbow compression fitting with the new tubing at the 

pressure switch. Screw the new straight connector into 

the AV22 and attach the tubing from the switch to the 

AV22.

Vertical deep well pumps come with a built-in AV21 and 

only need to be adjusted.

After the pump is primed and flowing water at a steady 

pressure you should open a few faucets and adjust the 

pressure control valve to the pressure listed in the chart. 

To increase pressure close the valve, AV15 or AV22, or 

turn the AV21 screw clockwise. 

See Chart 1

.

ALL SYSTEMS

Install HydroPro Water Systems Tank

While the tank is empty check the pre-charge 

air pressure with a tire pressure gauge. The 

tank pre-charge should be set 2 psi lower than 

the pump cut-in (turn on) pressure. On Goulds 

Water Technology HydroPro Water Systems 

tanks the valve cap is the primary seal so be 

sure to re-install the cap after checking air 

pressure. Avoid frequent air checking as you lose 1 – 2 

psi every time you check. Goulds Water Technology jet 

pumps are all supplied with 30 – 50 psi standard pressure 

switch settings.

Locate the tank on a firm, level surface.

A pressure relief valve is recommended for all systems, 

and mandatory for systems producing over 100 psi. It 

should be rated less than 100 psi but greater than the 

system pressure near the tank.

Make the piping connection between the pump dischar-

ge and the tank. Complete the piping by connecting to 

the house plumbing.

Note:

 Goulds Water Technology only sells the HydroPro 

Water System tanks. They are all shipped with a tank 

installation guide in the carton, please refer to it for more 

detailed tank instructions. If you are using a tank from 

another manufacturer please contact that company for 

specific instructions on their tank.

Galvanized tanks are installed the same as pre-charged 

tanks except they require an Air Volume Control (AVC) to 

replenish air lost through absorption. The AVC requires 

connection to a vacuum port on the pump. The suction 

side of the AVC must have a minimum 3" vacuum for 15 

seconds when the pump starts. Follow the instructions 

provided with the air volume control.

Priming a Shallow Well System

Priming means filling the pump and suction pipe with wa

-

ter. Most shallow well jet pumps handle air well and will 

evacuate air from the suction line but it may take several 

minutes to prime depending on depth to water, and pipe 

size and length. 

VENT THE PUMP FOR EASIER PRIMING!

It is easier to prime a pump if you allow all the air to esca-

pe from the pump and the pipes, the water cannot go in 

unless the air can escape! 

Remove the pipe plug or pressure gauge bushing in 

the discharge tee to fill the pump with water. On shallow 

well pumps you should remove the 

1

8

" pipe plug located 

between the suction and discharge ports to allow air to 

escape as you fill the casing with water. The port will be 

located on either the top of the casing or the top of the 

shallow well adapter. Fill the pump and as much of the 

suction pipe as possible with water through the dischar-

ge port.

Replace the 

1

8

" pipe plug and discharge gauge/bu-

shing. Open the faucet closest to the pump/tank a small 

amount to allow air to escape the system. Do not open it 

too much or the pump will expel too much water and you 

will have to reprime the pump casing. On jobs with long 

suction pipes you may have to add water to the pump 

casing several times to complete the priming process.

Go to Power Motor

.

Priming a Deep Well System

Priming a deep well system means filling the pump and 

the suction/pressure pipes with water. Deep well single 

stage and multi-stage pumps require a complete prime 

before starting. Filling the pipes with water before instal-

ling the pump will make priming faster and easier. 

VENT THE PUMP FOR EASIER PRIMING!

To insure a complete prime we recommend removing 

the angled 

1

8

" vent plug located just above the suction 

pipe on horizontal pumps. This will allow the air to easily 

escape as water enters. Our horizontal convertible deep 

well jets should be primed through a tee or the AV22 at 

the pump discharge. The tee is not supplied by Goulds 

Water Technology.

Our vertical deep well jet pumps have built-in pressure 

control valves. Priming is done through the pressure gau-

ge port on the pressure control valve. Most verticals have 

a vent plug located on the side of the motor adapter that 

vents the seal cavity which is the high point inside the 

pump. Removing this vent plug will make priming much 

easier.

AV22

ALL SYSTEMS

Fig. 4

AV15

AV21

Hazardous pressure can
cause personal injury or
property damage.

WARNING

Summary of Contents for Goulds J Series

Page 1: ...Jet Pumps INSTALLATION OPERATION AND TROUBLESHOOTING MANUAL INSTRUCTION MANUAL IM102R11...

Page 2: ...ng orsystemtoapressurehigherthanthe tank smaximumpressurerating Thiswilldamage thetank voidsthewarrantyandmaycreateaserious hazard Protecttanksfromexcessivemoistureand sprayasitwillcausethetanktorusta...

Page 3: ...e are two types of deep well jet assemblies twin pipe and packer systems Deep well pumps come in both vertical and horizontal designs and in single and multi stage models See Typical Installation Draw...

Page 4: ...eck valve is to the well the easier the system will prime To prevent over pumping a low yield well you can throttle a jet pump using a ball valve in the suction line You should install a compound pres...

Page 5: ...on Using smaller than recommended pipe may reduce gpm output The longer the pipe the worse the affect Install Packer Assembly To ease installation soak the 2 or 3 packer assembly in warm water to make...

Page 6: ...AVC to replenish air lost through absorption The AVC requires connection to a vacuum port on the pump The suction side of the AVC must have a minimum 3 vacuum for 15 seconds when the pump starts Foll...

Page 7: ...goes for a 230 volt hook up either wire can go on either Line terminal Re install the switch cover NOTE Motor voltage is NOT changed in the pressure switch See Fig 7 in Technical Data Check to insure...

Page 8: ...P3 53 3 27 30 70 AV22 and JDW FT5B 48 4 40 70 110 FP3 54 3 30 70 110 FT4B 44 4 31 30 60 FP2 48 2 35 30 60 AWJ2 FT4B 43 4 33 60 80 FP2 43 2 36 60 100 AV22KIT J10 FT4B 18 4 35 80 110 AV22 and JDW FT5B 4...

Page 9: ...DEPTH JET WELL CONTROL VALVE DEPTH PACKER CONTROL VALVE ASSEMBLY DIAMETER SETTING PSI TO JET ASSEMBLY DIAMETER SETTING PSI TO JET ADAPTER see fig 4 FT3 09 3 30 30 50 FP2 13 2 30 30 50 FT4B 13 4 30 30...

Page 10: ...48C04A06 115 230 1 1 6 12 6 6 3 990 25 15 SFJ05860 JRS7 JRD7 JB07 C48C05A06 115 230 1 1 5 14 8 7 4 1200 30 15 SFJ06860 JRS10 JRD10 JB10 C48C06A06 1 115 230 1 1 4 16 2 8 1 1400 30 20 Effective July 199...

Page 11: ...ess than pump capacity throttle a ball valve in suction line do not exceed 22 Hg to reduce pump capacity USE OF TAILPIPE ON DEEP WELL JET PUMPS If the capacity of a deep well jet pump exceeds the well...

Page 12: ...method or means of repair or replacement Buyer s failure to comply with Seller s repair or replacement directions shall terminate Seller s obligations under this Warranty and render this Warranty voi...

Page 13: ...Bombas de Inyecci n MANUAL DE INSTALACI N OPERACI N E IDENTIFICACI N Y RESOLUCI N DE PROBLEMAS MANUAL DE INSTRUCCI N IM102R11...

Page 14: ...cedemasiadoeltanque las tuber asoelsistemaaunapresi nsuperiorala clasificaci ndepresi nm ximadeltanque Elhacerloda ar eltanque anulalagarant aypuedecrearunpeligrograve Protejaalostanquescontrahumedady...

Page 15: ...profundos para elevaciones de m s de 25 pies y deben tener dos tuber as que vayan al pozo Hay dos tipos de conjuntos de inyecci n para pozos profundos los sistemas de tubo doble y los sistemas de obtu...

Page 16: ...ra impedir bombear en exceso un pozo de baja producci n usted puede estrangular una bomba de inyecci n con una v l vula de bola en la l nea de succi n Usted debe instalar un indicador compuesto de pre...

Page 17: ...n como los gpm disminuir n La bomba puede perder cebado f cil mente durante el bombeo debido a la restricci n Si se utiliza tuber a m s peque a que la recomendada podr a reducirse la salida de gpm Mie...

Page 18: ...nstalan de la misma mane ra que los tanques precargados excepto que requieren un control de volumen de aire AVC para reponer el aire perdido por absorci n El control de volumen de aire requiere una co...

Page 19: ...si n Co necte los alambres de la fuente de alimentaci n ya sea 115 230 dependiendo de la tensi n del motor a las terminales de l nea del interruptor por ca da de presi n Conecte el alambre verde o ala...

Page 20: ...0 90 AV22KIT J7 FT4B 18 4 30 90 110 o FT5B 47 4 28 30 70 FP3 53 3 27 30 70 AV22 and JDW FT5B 48 4 40 70 110 FP3 54 3 30 70 110 FT4B 44 4 31 30 60 FP2 48 2 35 30 60 AWJ2 FT4B 43 4 33 60 80 FP2 43 2 36...

Page 21: ...RADOR FT3 09 3 30 30 50 FP2 13 2 30 30 50 FT4B 13 4 30 30 50 AV15 JRD5 FT4B 31 4 30 30 70 FP2 31 2 30 30 60 AWJ2 o FT4B 08 4 30 60 90 FP2 08 2 30 60 80 AV22KIT FT5B 14 4 30 70 90 FT4B 14 4 27 30 60 FP...

Page 22: ...B07 C48C05A06 115 230 1 1 5 14 8 7 4 1200 30 15 SFJ06860 JRS10 JRD10 JB10 C48C06A06 1 115 230 1 1 4 16 2 8 1 1400 30 20 Fecha de vigencia julio de 1998 230 V nicamente DATOS T CNICOS Fig 7 PROCEDIMIEN...

Page 23: ...dad de la bomba estrangule una v lvula de bola en la l nea de succi n sin exceder 22 pulg de Hg para reducir la capacidad de la bomba USO DEL TUBO DE ASPIRACI N EN BOMBAS DE INYECCI N PARA POZOS PROFU...

Page 24: ...o reemplazo ser a total discreci n del Vendedor Si el Comprador no cumple con las instrucciones de reparaci n o reemplazo del Vendedor esto rescindir las obligaciones del Vendedor conforme a la presen...

Page 25: ...Pompes Jet MANUEL D INSTALLATION D UTILISATION ET DE D PANNAGE MANUEL D UTILISATION IM102R11...

Page 26: ...meetler servoir nejamaisutiliser unepressionexc dantlapressionnominale maximaledecedernier afindenepasl endommager annulerla garantieniconstituerungravedanger Prot gerler servoirdes claboussuresetdes...

Page 27: ...aux descendant dans le puits Il en existe deux types tuyaux jumel s ou tuyaux concentriques Les pompes pour puits profonds sont offertes en ver sions horizontales ou verticales multi tag es ou non Voi...

Page 28: ...la cr pine ou dans la pompe Dans le cas des installations pointe filtrante ou en puits tubulaires on peut poser un clapet de non retour pr s de la t te de puits ou de la pompe et utiliser le cuvelage...

Page 29: ...r le guide Ne pas poser de robinets de soupapes ni de filtres entre la pompe et le r servoir sauf s il s agit d un robinet vanne grand ouvert ou d un robinet tournant sph rique passage int gral La plu...

Page 30: ...its profonds Amorcer un syst me pour puits profonds signifie remplir d eau les tuyaux d aspiration et d alimentation en eau motrice ainsi que la pompe Les pompes multi tag es ou non pour puits profond...

Page 31: ...FONCTIONNER LA POMPE SEC CAR CELA L ENDOMMAGE RAIT ET ANNULERAIT LA GARANTIE ON DOIT TOUJOURS VERROUILLER LE DISJONCTEUR OU LE SECTIONNEUR SELON LE CAS DU CIRCUIT LEC TRIQUE EN POSITION OUVERTE HORS...

Page 32: ...6 3 34 30 60 J15 FT5B 11 4 40 70 140 FP3 18 3 34 60 90 AV22KIT FP3 21 3 34 90 150 AV22 et JDW FP3 24 3 39 100 170 FT4B 48 4 37 30 70 FP2 51 30 70 SJ07 et FT4B 47 4 40 70 90 FP2 50 2 40 70 90 AWD2 HSJ0...

Page 33: ...90 110 AV22 et JDW FT5B 47 4 27 30 70 S O FT5B 48 4 30 70 110 FT4B 44 4 31 30 60 FP2 48 2 35 30 60 FT4B 43 4 33 60 80 FP2 43 2 36 60 100 AWJ2 AV22KIT JRD10 FT4B 18 4 35 80 110 AV22 et JDW FT5B 49 4 28...

Page 34: ...C48C04A06 115 230 1 1 6 12 6 6 3 990 25 15 SFJ05860 JRS7 JRD7 JB07 C48C05A06 115 230 1 1 5 14 8 7 4 1200 30 15 SFJ06860 JRS10 JRD10 JB10 C48C06A06 1 115 230 1 1 4 16 2 8 1 1400 30 20 230 V seulement p...

Page 35: ...ire le d bit de celle ci l aide d un robinet tournant sph rique pos sur le tuyau d aspiration et r gl pour augmenter la d pression qui ne doit cependant pas d passer 22 po de Hg EMPLOI D UN TUYAU RALL...

Page 36: ...de r paration ou de remplacement Le non respect de l Acheteur de se conformer aux directives de r paration ou de remplacement du Vendeur mettra fin aux obligations du Vendeur sous cette Garantie et a...

Reviews: