Xtreme Power Conversion Corporation
Web/SNMP Cards
Page 27
UPS Management
Save Section
This section allows to save the current settings to non-volatile memory (Save) and/or to reboot the adapter (Re-
boot). Remember that the SNMP/Web adapter will revert to the last saved settings at reboot. Therefore, in order
to permanently modify the settings the configuration must be saved.
User Section
This section offers access to the user management web page. Note that this page becomes operative only for the
supervisor user (the only user enabled to perform user management).
SNMP Agent
The SNMP/Web adapters implement an SNMP Agent providing access to OIDs according to the MIB structure, and
may generate traps at the occurrence of specific events. This allows one or more NMSs (Network Management
Systems) to monitor, manage and control the UPS.
The SNMP Agent complies with the standard UPS-MIB as specified in RFC1628. Limited to the 3-ph
SNMP/Web plug-in adapter, additional information is available with the GESingle and GEParallel MIBs.
The SNMP/Web adapter implements both SNMP v1 and SNMP v2 protocols. Always remember that with these
protocols the information travel on the network in plain text. It is therefore recommended to disable the SNMP
Agent when this functionality is not used. Refer to the “Security” section of this manual for further details.
MIB Structure
RFC1628 MIB is available in the upsMIB group.
Additional UPS information is available in the GE MIB under the geUPS group