Xtreme Power Conversion Corporation
Web/SNMP Cards
Page 23
UPS Management
UPS Test page
This page presents allows to initiate a specific UPS test, and reports the status of the last performed test (if any).
The page includes a table with clear explanation of the test result reading. For an explanation of the various test
procedures please refer to the applicable UPS documentation
UPS Control page
The UPS control page mainly controls UPS shutdown and reboot behavior. As previously stated, these commands
will impact the UPS and may have effect on any load applied to the UPS. It is therefore important to fully under-
stand the consequences of any settings performed through this page.
Parameter Name
Description
Shutdown type
The action to be taken when the UPS is commanded to shutdown
1 – output
The output of the UPS is switched off
2 – system
The entire UPS system is switched off
Shutdown after delay
Specifies a time (in seconds) after which the UPS will shutdown
-1 disables the procedure
0 immediate shutdown
Startup after delay
Specifies a time (in seconds) after which the UPS will start-up
-1 disables the procedure
0 immediate start-up
Reboot
The UPS will shutdown immediately, and will remain off for the specified time (in
seconds), after which the UPS will restart
-1 disables the procedure
Auto-Restart
On – the UPS will restart right after the shutdown
Off – the UPS will not restart after the shutdown
Caution!
These commands may switch off the UPS output, therefore leaving the load with no power. Make sure
you fully understand the effect on the UPS and on the load before injecting any of these commands. Make sure
that it is safe to perform the described operation for both the UPS and the load.
UPS Config page
The page lists the main UPS configuration parameters. Normally, these parameters are pre-configured at the fac-
tory and there is no need to change them. Furthermore, forcing an incorrect configuration may impair the UPS
functionalities and severely affect the load. It is therefore recommended not to alter any configuration settings
unless informed and instructed to do so.
Operation page
This page lists the UPS operating conditions with reference to high-efficiency operation. The feature status can be
mapped to three conditions:
• Active: the UPS system is operating in high-efficiency mode
• Enabled/Inactive: the high-efficiency mode is enabled but currently inactive following scheduled activa-
tion and/or user control
• Disabled: high-efficiency mode is disabled
Additionally, the system load, the status of each module in the system and its operating times are also shown.
Configuration page
Both IEMi and eBoost can be configured for scheduled activation. Particularly, the user may define time intervals
when the system will operate in high-efficiency mode for weekdays (Saturday to Friday). These intervals are de-
fined by:
• Start Time:
The hour of the day after which high-efficiency operation is enabled.