NXRTi USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion Corporation (Rev 8/29/13)
Page 36
SPECIFICATIONS
MODEL
NXRTi-1000
NXRTi-2000
NXRTi-3000
CAPACITY
Capacity
1000VA / 800W
2000VA / 1600W
3000VA / 2400W
INPUT
Voltage
230 VAC, Single Phase Grounded
Frequency
45Hz-55Hz@50Hz / 55Hz-65Hz@60Hz
Power Factor
≥
0.98
Bypass Voltage Range
186 - 252 VAC
Harmonic Distortion
< 5% Non-Linear Load
OUTPUT
Rated Voltage
230VAC
Power Factor
0.8
Voltage
± 2%, Single Phase Grounded
Frequency
50/60 HZ ± 0.2
Crest Factor
3:1
Transfer Time
0 ms
Overload Capacity
150% for 30 sec; 200% for 300ms
Efficiency AC/DC/AC
≥
90%
BATTERY
UPS Battery Type
(2) 12V 9AH / 24V
(4) 12V 9AH / 48V
(6) 12V 9AH / 72V
UPS Charge Current
1A
Backup Time (minutes) *
½ Load
Full Load
½ Load
Full Load
½ Load
Full Load
UPS
12
5
12
5
12
5
+ (1) EBP
46
21
46
21
46
21
+ (2) EBP
88
40
88
40
88
40
+ (3) EBP
136
62
136
62
136
62
+ (4) EBP
188
86
188
86
188
86
+ (5) EBP
243
111
243
111
243
111
EBP Battery Type
2 x (2) 12V 9AH / 24V 2 x (4) 12V 9AH / 48V
2 x (6) 12V 9AH / 72V
EBP Charge Current
1A
*
for additional runtimes beyond (5) EBPs contact