NXRTi USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion Corporation (Rev 8/29/13)
Page 20
CAUTION: CONNECT ONLY BATTERY PACKS PROVIDING THE SAME DC VOLTAGE AS THE
UPS – PLEASE DOUBLE CHECK LABELING ON THE UPS AND BATTERY PACKS TO ASSURE
PROPER VOLTAGES ARE CONNECTED. CONNECTING THE INCORECT BATTERY PACK TO
THE UPS MAY RESULT IN DAMAGE TO THE UPS AND/OR BATTERY PACK THAT WILL VOID
THE WARRANTY.
•
Ensure that the UPS is disconnected from AC input and is off while connecting the
External Battery Packs. Ensure all battery breakers are in the “OFF” position.
•
Remove the EBP covers on the UPS and EBP. Connect the battery cable that comes with
the External Battery Pack between the External Battery Pack to the UPS.
•
Secure the DC battery cable to the rear of the UPS, and the rear of the EBP by using M3
x 8 screws provided (2 each per connector end).
•
Connect the input power cord from the EBP to an input AC utility source per
specifications.
•
Connect a second battery pack to the first EBP in the same fashion
if more than one is to
be installed.
•
Refer to Appendix A: Battery Pack User Manual for more details
2.
Connect SNMP card (option)
•
Remove the two screws securing the SNMP cover plate on the rear of the UPS, and slide
the SNMP NetAgentII card into the slot. Secure the card into the slot with the two
screws previously removed.
3.
Close the battery breakers on the Optional battery packs if installed.
4.
Connect the AC input cable to the UPS and connect the other end to an approved
grounded outlet. Once the UPS has been connected to an AC power source the internal
charger will start charging the UPS batteries, at this point the yellow LED is illuminated,
and the LCD displays “UPS OFF”. In this state the output voltage is zero, which means UPS
has no output. Please realize that although you may start using the UPS immediately,
maximum back-up time will still not be available, so it is recommended to charge the
batteries for a minimum of 6 hours before use.
5.
Start and configure the UPS
FRONT PANEL BUTTONS