Xtreme Power Conversion Corporation
M90S-4S User’s Manual
Page 54
Uninterruptible Power Supply
Figure 5-24 Warning screen
5.2.2 Setup-Battery setting list
Table 5-5: Setup-Battery Setting list
Setting Item
Sub Item
Explanation
Nominal Battery Voltage
--
Set battery nominal voltage
• 8x12V (Default)
•
9x12V
•
10x12V
MUST be set after UPS installation
Battery Capacity in Ah
--
Set battery capacity.
• 7, 9 (Default), 10, 12, 17, 26, 40, 65, 100Ah
MUST be set after UPS installation or Battery
capacity is changed.
Battery Groups
Set battery Groups
1 - default
Maximum Charging Current
--
Set battery maximum charging current (1~10)
• 4A (Default)
MUST be set after UPS installation or Battery
capacity is changed.
Battery Low/
Shutdown SETTING
Battery Low Voltage
Set battery low voltage (10.5~11.5V)x(battery
Number)
• 11.2V x Battery Number (Default)
Battery Low Capacity
Set battery low capacity (20~50%)
• 20% (Default)
Battery Shutdown Voltage
Set battery voltage point for system shutdown
in battery mode (10.0~11V) x (battery Number)
• 9.6V x Battery Number (Default)