Xtreme Power Conversion Corporation
M90S-4S User’s Manual
Page 52
Uninterruptible Power Supply
Bypass
Mode
--
Set bypass mode
• Disable
• Enable (Default)
MUST be reviewed after UPS instal-
lation.
If you need the Bypass power when
UPS is OFF, please enable it.
Converter
Mode
--
Set converter mode
• Disable (Default)
• Enable
Set Output Frequency
• 50Hz (Default)
• 60Hz
Battery
Mode Delay
Time
--
Set system shutdown delay time in
battery mode
(Disable or 10~990Min).
• Disable (Default)
• Not 0: Enable
When this feature is enabled, UPS
will shut off output after UPS oper-
ates in Battery mode for certain
seconds.
Cold Start
--
Set system shutdown time
(0.2~99min)
• 0.2 min (Default)
This delay time will start counting
when the
CONTROL-Shutdown Restore com-
mand is executed.
System
Shutdown
Time
--
Set system restore time
(0~9999min)
• 1 min (Default)
This delay time will start counting
after shutdown time is elapsed
when the CONTROL-Shutdown
Restore command is executed.
Redundancy
--
Set redundancy
Redundancy: the QTY of redundant
UPS module(0~9)
• 0(Default)
MUST be set after UPS installation
Charger Test --
Set charger test
• Disable (Default)
• Enable