6.9
Terminating the Remote LED Indicator Conductors
Refer to Figure 6-5 for the LED terminal location on the termination card.
Connect the LED + and – conductors from the Remote Indicator (AutoPulse P/N 430572). Observe correct
polarity.
LED Terminal Block (X2)
Figure 6-5: Remote indicator connections
6.10 Terminating IDNet Conductors
Refer to Figure 6-5 for the COMM + / - connections on the termination card. There are 4 terminal positions
provided to allow “In/Out” wiring.
a. Connect the IDNet SLC conductors to the appropriate terminals of termination card. Observe correct
polarity.
Terminal Block (X1)
COMM - 1
COMM + 2
IDNet
SLC to next device
IDNet
SLC from
Control Panel or
Previous Device
Figure 6-6: SLC conductor connections
6.11 Terminating the Power Supply Monitor Conductors
a. Refer to Figure 6-4 for the PS Mon + and PS MON – connections on the termination card.
b. Connect PS MON conductors to terminals 5 and 6 (of TB X1) as demonstrated in figure below. Ensure 47
K Ohm ¼ W resistor is connected at terminal block of remote power supply.
Terminal Block (X1)
Figure 6-7: Remote power supply trouble output connectors