ICAM IFT-P Product Guide
ICAM by Xtralis
42
www.xtralis.com
LOAD DEFAULTS: Load Defaults
Minimum Access Code Required:
Level 2
This menu option will enable the user to reload all factory defaults for all configuration parameters under the
Configuration and Sector Alarms menus. It is recommended that the system configuration is saved prior to
applying this menu option.
MAINTENANCE: Maintenance Mode
Minimum Access Code Required:
None
Use the Parameter UP & DOWN buttons (Isolate and Scan) to inspect any item in the maintenance list.
Parameter
Description
LASERIN
Current smoke value for the laser detector output
MOD1 IN
Identification number of Module 1
MOD2 IN
Identification number of Module 2
MOD3 IN
Identification number of Module 3
MOD4 IN
Identification number of Module 4
MOD5 IN
Identification number of Module 5
Table D-9: Maintenance Parameters
TEST OUTPUTS: Testing Mode
Minimum Access Code Required:
Level 2
This menu item enables the user to manually increase or decrease smoke levels for the detector in order to
simulate a real fire event. This enables the user to test the responses of the detector to a fire event. Please
note that all alarms and relays will operate as if the system is reacting to a real fire event.