ICAM by Xtralis
ICAM IFT-P Product Guide
www.xtralis.com
21
The Analogue Output Module is configured using Xtralis VSC.
The optional remote display may also be used as follows:
Table A-2: 8-Channel Output Module Configuration Parameters
Menu Item
Parameter
Value
SETUP
(MODULE n)
Set to ANOUT 8
CONFIGURE
(MOD n)
SMOKE X or FLOW X
(GAIN X)
Applies to Smoke only.
G = A/O where:
l
G = Gain
l
A = Maximum Output Current
l
O = Obscuration reading
corresponding to maximum
output current
Examples:
l
Set GAIN X to 1 for 20%/m
(1 = 20mA / 20%/m)
l
Set GAIN X to 10 for 2%/m
(10 = 20mA / 2%/m)
l
Set GAIN X to 100 for 0.2%/m
(100 = 20mA / 0.2%/m)
To access the Setup menu, follow these steps:
1. Press
MENU
.
2. Use Parameter
UP
&
DOWN
buttons to reach
SETUP
.
3. Press
ENTER
.
4. Use Value
UP
&
DOWN
buttons to enter the Level 2 Access Code.
To access the Configure menu, follow these steps:
1. Press
MENU
.
2. Use Parameter
UP
&
DOWN
buttons to reach
CONFIGURE
.