Xpelair GX6 Installation And Maintenance Instructions Manual Download Page 10

The fan is operated by a remote 

switch.

The fan indicator light shows when it 

is switched on.

An integral timer provides an 

adjustable overrun period after the 

fan is switched off.

Condensation operation

The fan operates automatically if the 

relative humidity is above the set 

level.

The integral timer provides an 

adjustable overrun period after the 

relative humidity level has fallen.

Switched operation

A manual operation remote switch 

starts the fan. The fan indicator light 

shows when it is switched on.

The integral timer provides an 

adjustable overrun period after the 

fan has been switched off.

Condensation operation

The fan operates automatically at low 

speed if the relative humidity rises 

above the set level.

The integral timer provides an 

adjustable overrun period after the 

fan has been switched off.

Boost operation

The integral pull cord switches the fan

on to run at high speed. The fan 

indicator light shows when high

speed has been selected.

A remote switch may be used as an 

alternative to the pull cord. If this is 

used, cut off the pull cord, after

ensuring that the pull cord switch is in 

the “off” position.

This fan is operated by a remote 

switch.

This fan is operated by a remote 

switch. 

Before making any adjustments,

isolate the fan completely from the

mains electricity supply.

Adjusting the timer overrun

The overrun timer is factory preset at

approximately 20 minutes. The time is

adjustable between approximately

2 to 20 minutes.

1. Remove the back draught shutter/

grille assembly (see “Mounting the 

fan in the hole” section).

2. Turn the adjuster marked “T” anti-

clockwise to reduce the timer overrun 

(see Fig.H).

3. Turn the adjuster clockwise to increase

the timer overrun (see Fig.H).

4. Replace the back draught shutter/

grille assembly (see “Mounting the 

fan in the hole” section).

Adjusting the humidistat setting

The internal humidity sensor is factory

set at approximately 70%. The level is

adjustable between approximately

50% and 90% relative humidity.

Remove the back draught shutter/grille

assembly (see “Mounting the fan in the

hole” section).

Turn the adjuster marked “H” anti-

clockwise to decrease the relative

humidity level of the room (see Fig. 1).

Turn the adjuster clockwise to increase

the relative humidity level of the room

(see Fig.l).

Replace the back draught shutter/grille

assembly (see “Mounting the fan in the

hole” section).

Trickle ventilation is equivalent to that

provided by an airbrick or similar device.

1. Remove the back draught shutter/

grille assembly (see “Mounting the 

fan in the hole” section).

2. HOLD THE SHUTTER VANES FULLY

OPEN.

3. Push down firmly on the trickle vent 

catch until it clicks into position then 

release the shutter vanes. (See

Fig.F item 6).

4. Pull the trickle vent catch towards you

until it clicks into position.

5. Refit the back draught shutter/grille 

assembly, see “Mounting the fan in 

the hole” section, ensuring that the

actuator lever is in the “fully down” 

position.

A QUALIFIED ELECTRICIAN MUST

CARRY OUT ALL CLEANING.

NOTE: THE FAN WILL CONTINUE TO

OPERATE WITH THE INNER GRILLE

REMOVED HENCE IT MUST BE

ISOLATED COMPLETELY FROM THE

MAINS BEFORE ANY WORK IS

CARRIED OUT.

1.

Before cleaning, isolate the fan 

completely from the mains 

electricity supply. Allow 3 minutes 

for the impeller to stop rotating 

and the powered shutter to close. 

(Cleaning on the GXC6 and GXS6 

can begin once the impeller has 

stopped rotating).

2. Remove the back draught shutter/

grille assembly by pressing the 

release catch located on the side of 

the unit with a 6mm screwdriver or 

coin, whilst pulling the grille forward. 

To remove the back draught shutter,

lay face down and pull shutter 

forwards see Fig.G1 and Fig.G2.

3. To remove the impeller. Unscrew the 

central screw and remove it together 

with the washer. Place screw and 

washer to one side.

4. To clean the impeller, either wipe it 

with a damp, lint free cloth or wash it 

in warm soapy water. Thoroughly

dry the impeller and refit.                

Replace the screw and washer 

ensuring that they are securely fitted.

5. Clean the back draught shutter/grille 

assembly and impeller in warm soapy 

water. 

Do not use strong detergents

or chemical cleaners.

6. Thoroughly dry the back draught 

shutter/grille assembly and refit by 

sliding the grille back over the realise

catches, the catches will locate in and

secure the grille (see Fig.G3 and 

Fig.G4). For GXS6 MODEL:

Ensure 

that the actuator lever is in the “fully 

down” position.

7.

Do not immerse the fan in water or 

other liquids to clean any other 

parts of the fan.

Never use strong solvents to clean

the fan.

Apart from cleaning, no other

maintenance is required.

1.  Back draught shutter.
2.  Fan assembly.
3.  Outer grille
4.  Ladder strips.
5. Terminal cover
6. Trickle vent catch
7. Rear cable entry.
8.  Top cable entry.
9.  Rating plate.
10. Lugs for screw mounting.
11. Grille.
12. Screw hole caps.
13. Actuator lever (GXS6 model only).

GX6T / GXC6T / GX6HT and

GX6HT2 only

GX6T

GX6HT2

To allow trickle ventilation

Trickle ventilation

To fully close the shutters and

stop any back draught

GX6HT

GXS6

GX6 (IP25)

Maintenance

Components Fig. D

The fan is operated by a remote 

switch.

The fan indicator light shows when it 

is switched on.

An integral timer provides an 

adjustable overrun period after the 

fan is switched off.

Condensation operation

The fan operates automatically if the 

relative humidity is above the set 

level.

The integral timer provides an 

adjustable overrun period after the 

relative humidity level has fallen.

Switched operation

A manual operation remote switch 

starts the fan. The fan indicator light 

shows when it is switched on.

The integral timer provides an 

adjustable overrun period after the 

fan has been switched off.

Condensation operation

The fan operates automatically at low 

speed if the relative humidity rises 

above the set level.

The integral timer provides an 

adjustable overrun period after the 

fan has been switched off.

Boost operation

The integral pull cord switches the fan

on to run at high speed. The fan 

indicator light shows when high

speed has been selected.

A remote switch may be used as an 

alternative to the pull cord. If this is 

used, cut off the pull cord, after

ensuring that the pull cord switch is in 

the “off” position.

This fan is operated by a remote 

switch.

This fan is operated by a remote 

switch. 

Before making any adjustments,

isolate the fan completely from the

mains electricity supply.

Adjusting the timer overrun

The overrun timer is factory preset at

approximately 20 minutes. The time is

adjustable between approximately

2 to 20 minutes.

1. Remove the back draught shutter/

grille assembly (see “Mounting the 

fan in the hole” section).

2. Turn the adjuster marked “T” anti-

clockwise to reduce the timer overrun 

(see Fig.H).

3. Turn the adjuster clockwise to increase

the timer overrun (see Fig.H).

4. Replace the back draught shutter/

grille assembly (see “Mounting the 

fan in the hole” section).

Adjusting the humidistat setting

The internal humidity sensor is factory

set at approximately 70%. The level is

adjustable between approximately

50% and 90% relative humidity.

Remove the back draught shutter/grille

assembly (see “Mounting the fan in the

hole” section).

Turn the adjuster marked “H” anti-

clockwise to decrease the relative

humidity level of the room (see Fig. 1).

Turn the adjuster clockwise to increase

the relative humidity level of the room

(see Fig.l).

Replace the back draught shutter/grille

assembly (see “Mounting the fan in the

hole” section).

Trickle ventilation is equivalent to that

provided by an airbrick or similar device.

1. Remove the back draught shutter/

grille assembly (see “Mounting the 

fan in the hole” section).

2. HOLD THE SHUTTER VANES FULLY

OPEN.

3. Push down firmly on the trickle vent 

catch until it clicks into position then 

release the shutter vanes. (See

Fig.F item 6).

4. Pull the trickle vent catch towards you

until it clicks into position.

5. Refit the back draught shutter/grille 

assembly, see “Mounting the fan in 

the hole” section, ensuring that the

actuator lever is in the “fully down” 

position.

A QUALIFIED ELECTRICIAN MUST

CARRY OUT ALL CLEANING.

NOTE: THE FAN WILL CONTINUE TO

OPERATE WITH THE INNER GRILLE

REMOVED HENCE IT MUST BE

ISOLATED COMPLETELY FROM THE

MAINS BEFORE ANY WORK IS

CARRIED OUT.

1.

Before cleaning, isolate the fan 

completely from the mains 

electricity supply. Allow 3 minutes 

for the impeller to stop rotating 

and the powered shutter to close. 

(Cleaning on the GXC6 and GXS6 

can begin once the impeller has 

stopped rotating).

2. Remove the back draught shutter/

grille assembly by pressing the 

release catch located on the side of 

the unit with a 6mm screwdriver or 

coin, whilst pulling the grille forward. 

To remove the back draught shutter,

lay face down and pull shutter 

forwards see Fig.G1 and Fig.G2.

3. To remove the impeller. Unscrew the 

central screw and remove it together 

with the washer. Place screw and 

washer to one side.

4. To clean the impeller, either wipe it 

with a damp, lint free cloth or wash it 

in warm soapy water. Thoroughly

dry the impeller and refit.                

Replace the screw and washer 

ensuring that they are securely fitted.

5. Clean the back draught shutter/grille 

assembly and impeller in warm soapy 

water. 

Do not use strong detergents

or chemical cleaners.

6. Thoroughly dry the back draught 

shutter/grille assembly and refit by 

sliding the grille back over the realise

catches, the catches will locate in and

secure the grille (see Fig.G3 and 

Fig.G4). For GXS6 MODEL:

Ensure 

that the actuator lever is in the “fully 

down” position.

7.

Do not immerse the fan in water or 

other liquids to clean any other 

parts of the fan.

Never use strong solvents to clean

the fan.

Apart from cleaning, no other

maintenance is required.

1.  Back draught shutter.
2.  Fan assembly.
3.  Outer grille
4.  Ladder strips.
5. Terminal cover
6. Trickle vent catch
7. Rear cable entry.
8.  Top cable entry.
9.  Rating plate.
10. Lugs for screw mounting.
11. Grille.
12. Screw hole caps.
13. Actuator lever (GXS6 model only).

GX6T / GXC6T / GX6HT and

GX6HT2 only

GX6T

GX6HT2

To allow trickle ventilation

Trickle ventilation

To fully close the shutters and

stop any back draught

GX6HT

GXS6

GX6 (IP25)

Maintenance

Components Fig. D

Ǿ ʌĮȡȠȪıĮ ıȣıțİȣȒ įİȞ ʌȡȠȠȡȓȗİIJĮȚ ȖȚĮ

ȤȡȒıȘ Įʌȩ ȐIJȠȝĮ

 (

ȝİIJĮȟȪ ȐȜȜȦȞ ʌĮȚįȚȐ

țĮȚ ȐIJȠȝĮ ȝİ țȜȠȞȚıȝȑȞȘ ȣȖİȓĮ

)

ȝİ

ȝİȚȦȝȑȞİȢ ijȣıȚțȑȢ

,

ĮȚıșȘIJȚțȑȢ Ȓ ȞȠȘIJȚțȑȢ

įİȟȚȩIJȘIJİȢ Ȓ ȑȜȜİȚȥȘ ʌİȓȡĮȢ țĮȚ ȖȞȫıİȦȞ

,

İțIJȩȢ ĮȞ İʌȚIJȘȡȠȪȞIJĮȚ Ȓ țĮșȠįȘȖȠȪȞIJĮȚ ȦȢ

ʌȡȠȢ IJȘ ȤȡȒıȘ IJȘȢ ıȣıțİȣȒȢ Įʌȩ ȐIJȠȝȠ

ʌȠȣ İȓȞĮȚ ȣʌİȪșȣȞȠ ȖȚĮ IJȘȞ ĮıijȐȜİȚȐ

IJȠȣȢ

.

ȉĮ ʌĮȚįȚȐ șĮ ʌȡȑʌİȚ ȞĮ

İʌȚIJȘȡȠȪȞIJĮȚ

,

ȑIJıȚ ȫıIJİ ȞĮ įȚĮıijĮȜȓȗİIJĮȚ

ȩIJȚ įİȞ șĮ ȤȡȘıȚȝȠʌȠȚȒıȠȣȞ IJȘ ıȣıțİȣȒ

ıĮȞ ʌĮȚȤȞȓįȚ

.

The fan is operated by a remote 

switch.

The fan indicator light shows when it 

is switched on.

An integral timer provides an 

adjustable overrun period after the 

fan is switched off.

Condensation operation

The fan operates automatically if the 

relative humidity is above the set 

level.

The integral timer provides an 

adjustable overrun period after the 

relative humidity level has fallen.

Switched operation

A manual operation remote switch 

starts the fan. The fan indicator light 

shows when it is switched on.

The integral timer provides an 

adjustable overrun period after the 

fan has been switched off.

Condensation operation

The fan operates automatically at low 

speed if the relative humidity rises 

above the set level.

The integral timer provides an 

adjustable overrun period after the 

fan has been switched off.

Boost operation

The integral pull cord switches the fan

on to run at high speed. The fan 

indicator light shows when high

speed has been selected.

A remote switch may be used as an 

alternative to the pull cord. If this is 

used, cut off the pull cord, after

ensuring that the pull cord switch is in 

the “off” position.

This fan is operated by a remote 

switch.

This fan is operated by a remote 

switch. 

Before making any adjustments,

isolate the fan completely from the

mains electricity supply.

Adjusting the timer overrun

The overrun timer is factory preset at

approximately 20 minutes. The time is

adjustable between approximately

2 to 20 minutes.

1. Remove the back draught shutter/

grille assembly (see “Mounting the 

fan in the hole” section).

2. Turn the adjuster marked “T” anti-

clockwise to reduce the timer overrun 

(see Fig.H).

3. Turn the adjuster clockwise to increase

the timer overrun (see Fig.H).

4. Replace the back draught shutter/

grille assembly (see “Mounting the 

fan in the hole” section).

Adjusting the humidistat setting

The internal humidity sensor is factory

set at approximately 70%. The level is

adjustable between approximately

50% and 90% relative humidity.

Remove the back draught shutter/grille

assembly (see “Mounting the fan in the

hole” section).

Turn the adjuster marked “H” anti-

clockwise to decrease the relative

humidity level of the room (see Fig. 1).

Turn the adjuster clockwise to increase

the relative humidity level of the room

(see Fig.l).

Replace the back draught shutter/grille

assembly (see “Mounting the fan in the

hole” section).

Trickle ventilation is equivalent to that

provided by an airbrick or similar device.

1. Remove the back draught shutter/

grille assembly (see “Mounting the 

fan in the hole” section).

2. HOLD THE SHUTTER VANES FULLY

OPEN.

3. Push down firmly on the trickle vent 

catch until it clicks into position then 

release the shutter vanes. (See

Fig.F item 6).

4. Pull the trickle vent catch towards you

until it clicks into position.

5. Refit the back draught shutter/grille 

assembly, see “Mounting the fan in 

the hole” section, ensuring that the

actuator lever is in the “fully down” 

position.

A QUALIFIED ELECTRICIAN MUST

CARRY OUT ALL CLEANING.

NOTE: THE FAN WILL CONTINUE TO

OPERATE WITH THE INNER GRILLE

REMOVED HENCE IT MUST BE

ISOLATED COMPLETELY FROM THE

MAINS BEFORE ANY WORK IS

CARRIED OUT.

1.

Before cleaning, isolate the fan 

completely from the mains 

electricity supply. Allow 3 minutes 

for the impeller to stop rotating 

and the powered shutter to close. 

(Cleaning on the GXC6 and GXS6 

can begin once the impeller has 

stopped rotating).

2. Remove the back draught shutter/

grille assembly by pressing the 

release catch located on the side of 

the unit with a 6mm screwdriver or 

coin, whilst pulling the grille forward. 

To remove the back draught shutter,

lay face down and pull shutter 

forwards see Fig.G1 and Fig.G2.

3. To remove the impeller. Unscrew the 

central screw and remove it together 

with the washer. Place screw and 

washer to one side.

4. To clean the impeller, either wipe it 

with a damp, lint free cloth or wash it 

in warm soapy water. Thoroughly

dry the impeller and refit.                

Replace the screw and washer 

ensuring that they are securely fitted.

5. Clean the back draught shutter/grille 

assembly and impeller in warm soapy 

water. 

Do not use strong detergents

or chemical cleaners.

6. Thoroughly dry the back draught 

shutter/grille assembly and refit by 

sliding the grille back over the realise

catches, the catches will locate in and

secure the grille (see Fig.G3 and 

Fig.G4). For GXS6 MODEL:

Ensure 

that the actuator lever is in the “fully 

down” position.

7.

Do not immerse the fan in water or 

other liquids to clean any other 

parts of the fan.

Never use strong solvents to clean

the fan.

Apart from cleaning, no other

maintenance is required.

1.  Back draught shutter.
2.  Fan assembly.
3.  Outer grille
4.  Ladder strips.
5. Terminal cover
6. Trickle vent catch
7. Rear cable entry.
8.  Top cable entry.
9.  Rating plate.
10. Lugs for screw mounting.
11. Grille.
12. Screw hole caps.
13. Actuator lever (GXS6 model only).

GX6T / GXC6T / GX6HT and

GX6HT2 only

GX6T

GX6HT2

To allow trickle ventilation

Trickle ventilation

To fully close the shutters and

stop any back draught

GX6HT

GXS6

GX6 (IP25)

Maintenance

Components Fig. D

Summary of Contents for GX6

Page 1: ...and maintenance instructions Retain for future reference GB F D NL I a NO GR Internal External Wall Window Fan Range Do read all the instruction leaflet before commencing installation Do install each...

Page 2: ...A B C D GLASS WINDOW 6 see F 13...

Page 3: ...E1 E2 E3...

Page 4: ...G1...

Page 5: ...G3 G2...

Page 6: ...wJ A B hJ c E g Hy 6H w9 enJ 550 9 kd8d i foK 0 C Ed i K 3d d hBz h Iz f Dz x K yE 3d o E t i g eG F hBz E k 3d E E BxiE f oiE 0 C Ed x h e F 7I fo B x E E fr h Iz F 0 dD 1 E xC F I haBxiE 0d h x K i...

Page 7: ...F xD diE L I F f D Ed K yE u E i K d 8 E1 d 6du 5 eC F xui 4 E Ld F E 3d yH he 4d I 4d 3d kdCd I h I h kdCd KxE KyE d E I kd d I 5 x hBz FI KxE E KyE iF 4 I F u 5 h 4 3d xui 4 3d d e E x F xD di E d...

Page 8: ...LEAVE THIS LEAFLET WITH THE FAN FOR THE BENEFIT OF THE USER Installing the fan Description GX6 GXC6 GXC6T GX6T GX6HT GX6HT2 GXS6 GX6 IP25 What the installer will need If window mounting the fan you wi...

Page 9: ...n the outer grille is aligned with the hole in the wall 2 Mark the positions of the fixing holes in the top right and bottom left corners 3 Drill the holes and insert anchor fixings to suit the wall 4...

Page 10: ...airbrick or similar device 1 Remove the back draught shutter grille assembly see Mounting the fan in the hole section 2 HOLD THE SHUTTER VANES FULLY OPEN 3 Push down firmly on the trickle vent catch u...

Page 11: ...c voyant incorpor Pour un d clenchement appareil d appoint ext rieur il faut pr voir deux commutateurs Tournevis grosse lame de 6 mm tournevis d lectricien lame de 3 mm tournevis Pozidriv n 1 et 2 Une...

Page 12: ...2 Poser le c ble entre le bouton sectionneur et l emplacement du ventilateur en passant par l interrupteur de marche arr t Cf Fig E1 SW1 Cf Fig E2 et l interrupteur de relais ext rieur SW1 Cf Fig E3...

Page 13: ...elister Installering i vindu Kun for Australia Installering i vegg Hvis du har tilgang til kjerneborutstyr Hvis du ikke har tilgang til kjerneborutstyr Montere viften i hullet Fig C Ved feste med skru...

Page 14: ...mottrekksklaffer for umiddelbar pning og lukking Innstilling av dryppventilering For bruk med fjerntliggende bryter Utsug ved enkel hastighe Innstilling av dryppventilering IP25 inngangsvern En skill...

Page 15: ...rsi Nei modelli GXC6 e GXS6 l operazione di pulizia pu essere iniziata non appena la girante ha smesso di ruotare 2 Togliere il gruppo serranda di controtiraggio grata premendo i fermi di sgancio ubic...

Page 16: ...t in einen Rauchkanal abgef hrt werden der f r den Abzug von Abgasen nichtelektrisch betriebener Ger te vorgesehen ist F r die Ausleitung von Abluft und Zuluftstr mungsgeschwindigkeite n m ssen die Vo...

Page 17: ...trattore per l installazione In caso di fissaggio con i listelli a scala In caso di installazione in finestra Solo per l Australia In caso di installazione a parete Se si dispone di un allargatore di...

Page 18: ...entellinare Per funzionamento con interruttore a distanza Temporizzatore igrostato incorporato Estrazione ad una velocit Impostazione di ventilazione centellinare Per funzionamento con interruttore a...

Page 19: ...Siehe Abb F Punkt 6 4 Trek de klem van de druppelventilatie naar u toe tot hij op z n plaats klikt 5 Breng de jalouzie afsluiter roosterassemblage weer aan zie de sectie Bevestiging van de ventilator...

Page 20: ...te of badkamer moet het zo zijn geplaatst dat het niet door personen die een bad of douche nemen kan worden aangeraakt 1 Controleer of er geen verborgen leidingen bijvoorbeeld elektriciteit gas water...

Reviews: