USER MANUAL - OPTIMA UPS 6K/ 10K (ENGLISH)
______________________________________________________________________________________________________________________
20150610 Tower-Rack 6K-10K ISOTX
- 36
13: BATTERY VOLTAGE ADJUSTMENT
LCD
Parameter 2:
Select “
Add
” or “
Sub
” for adjusting battery voltage (Add or
Reduce)
Parameter 3:
available adjustment value is from 0Vdc to 5.7Vdc. factory
set value is 0V.
*** WE STRONGLY RECOMMEND TO NOT CHANGE THIS FACTORY SET
VALUE **
14: BATTERY CHARGER ADJUSTMENT
LCD
Parameter 2:
Select “
Add
” or “
Sub
” for adjusting battery charger voltage
(Add or Reduce)
Parameter 3:
available adjustment value is from 0V a 9.9V. Factory set
value is 0Vdc
NOTE:
*Before changing this value batteries must be disconnected from UPS so
that charger output voltage can be measured without batteries interference.
*** WE STRONGLY RECOMMEND TO NOT CHANGE THIS FACTORY SET
VALUE **
15: OUTPUT VOLTAGE ADJUSTMENT
LCD
Parameter 2:
Select “
Add
” or “
Sub
” for adjusting battery charger voltage
(Add or Reduce)
Parameter 3
available adjustment value is from 0V a 6.4V. Factory set
value is 0V.