11.- UPS CONFIGUIRATION
* This menu is activated by simultaneous selection of “Test/Up” + “Mute/Down” keys during 1 second or longer when UPS
is in OFF or BYPASS mode.
Configurable
functions
according
to
UPS
mode
Code Description
Bypass
AC
ECO
CVCF Battery
Battery
Test
1
Output Voltage
●
2
Output Frequency
●
3
Voltage Range for BYPASS
●
4
Frequency Range for BYPASS
●
5
ECO Mode: Enable and Disable
●
6
Voltage Range for ECO mode
●
7
Frequency Range ECO mode
●
8
BYPASS mode
●
●
9
Battery Backup Security Time
●
●
●
●
●
●
10
Programmable Output
(note 1)
●
●
●
●
●
●
11
Programmable Output Settings
(note 1)
●
●
●
●
●
●
11
NO-Battery startup function
●
●
●
●
●
●
13
Battery Voltage adjustment
●
●
●
●
●
●
14
Battery Charger Voltage adjustment
●
●
●
●
●
●
15
UPS output voltage adjustment
●
●
●
”
●
” configurable parameter according to each UPS working mode.
note 1:
In ISOTX models, function 10 and 11 are not
available.
Configuration
menu
texts
Text Description
ADD
Add (Añadir)
ATO
Auto (Automático)
BAT
Battery (Batería)
DIS
Disable (Des-habilitado)
ENA
Enable (Habilitado)
FBD
Not allowed (No permitido)
CF
CVCF mode (Modo Convertidor de Frecuencia)
NCF
Normal mode (not CVCF mode)
ON
On
OFF
Off
OPN
Allow (Permitido)
PAR
Parallel (Paralelo)
RES
Reserved (Reservado)
SUB
Subtract