4.- UPS INSTALLATION: SINGLE UPS - TERMINAL BLOCK
AC
LINES
CONNECTION
PROCEDURE
• Make sure the UPS is Off before starting the installation.
• Remember to check all wires to be connected are not powered (including external batteries).
UPS terminal block preparation
Remove cover of terminal block at the UPS rear panel, identified as 12 in rear panel section of this manual
DO NOT use a wall power outlet to plug UPS to AC Line as usually ratings of this kind of outlets are not enough to power
6KVA UPS. UPS Input wire must be connected by breaker protected line to electric panel board.
UPS Input and Output Connection
Connect input and output ground wires to proper place on the UPS chassis on both sides of terminal blocks. Ground wires
must be FIRST to be connected and LAST to be disconnected.
Connect UPS input and output wires according to your UPS model or configuration as described in following figures:
TOWER TYPE 6 / 10K
TOWER TYPE 6K / 10K ISO - WITH INTERNAL ISOTX
INT. BLOCK DIAGRAM
•
Output 1: Output with Galvanic Isolation, 110Vac between phase and Neutral with 50% of total UPS capacity.
•
Output 2: Output with Galvanic Isolation, 110Vac between phase and Neutral with 50% of total UPS capacity.