Installation
36
975-0126-02-01
Step 8: Performing Checks Prior to Initial Start-Up
Before testing your installation, ensure these conditions are met:
❐
Chassis and AC grounds are properly installed.
❐
AC input connections and AC output connections are wired correctly on the
terminal block and not reversed.
❐
Positive (+) battery cable is connected to the house bank positive (+) battery
terminal through the DC fuse and disconnect switch or DC circuit breaker.
❐
Negative (–) battery cable is connected to the house bank negative (–) battery
terminal.
❐
House battery voltage is within the proper range for this unit
(10.3–15.3 volts DC).
❐
DC disconnect switch or breaker is turned off.
❐
Echo Charger disconnect switch is off or fuse is removed.
❐
Echo Charger connections are correct: positive (+) cable runs from the Echo
Charger to the positive terminal of the engine battery.
❐
Both the house battery and the engine battery negative terminals are
connected to the engine negative terminal/bus.
❐
AC input and output breakers are turned off.
❐
All connections are tight.