Installation
22
975-0126-02-01
Connecting the AC Output Wires
To make the AC output wiring connections:
1.
Remove one of the AC knockouts from the front or side of the unit. Do not
leave the knockout inside the wiring compartment
2.
Install a strain-relief clamp in the AC knockout.
3.
Run the AC wiring through the strain-relief clamp.
4.
Strip approximately 2 inches (50 mm) off the jacket from the AC cable and
separate the three wires.
5.
Using the 1/4" blade slot screwdriver, loosen the wire attachment screws on
the AC output terminals. Do not remove the screws.
6.
Insert the line wire into "L", the neutral wire into "N", and the ground wire
into ground (
)
, as shown in Figure 6. Observe the color codes described in
Table 4.
7.
Tighten the wire attachment screws. Leave some slack wire inside the wiring
box.
8.
Secure the strain-relief clamp on the AC output cable jacket.
9.
Attach the wiring compartment cover panel and tighten the four screws.
10. Connect the outgoing AC wires to an AC load panel equipped with circuit
breakers.
Figure 6
AC In and AC Out: Hardwiring Completed
CAUTION: Risk of equipment damage
Do not connect the output of the inverter to any incoming AC source.
Important:
The applicable installation code may not allow you to run the AC
input and AC output wiring through the same AC knockout.
Summary of Contents for MS2000
Page 1: ...MS2000 Sine Wave Inverter Charger Installation Guide MS2000 ...
Page 2: ......
Page 3: ...MS2000 Sine Wave Inverter Charger Installation Guide ...
Page 8: ...iv 975 0126 02 01 ...
Page 16: ...xii ...
Page 18: ...xiv ...
Page 45: ...Installation 975 0126 02 01 27 Figure 9 Completed DC Wiring ...
Page 57: ...Installation 975 0126 02 01 39 Figure 18 Inverter Charger Dimensions 14 2 361 ...
Page 75: ......