Configuration
975-0125-02-01
3–19
In another example where the bank size is 500 Ah or more and the Max Chg rate
is set to 50%, the calculation would be: 500 ÷
5 or 100 amps × 50%. The total
output would be 50 amps with 40 amps going to the house battery bank and 10
amps to the engine battery.
Load Sense
Configurable setting
This setting lets you enable or disable the load sensing function.
When to use
Enable this setting if you want the inverter to conserve battery power when there
are small loads or no loads applied.
Outcome
A small load like a clock display on a microwave may not get power. When loads
are below the load sense threshold, the inverter will turn off the output to save
battery power.
Equalize
See a description of this feature on page 3–12.
Clear Faults
See a description of this feature on page 3–15.
View Device Info
For more information on this sub menu, Device Information, see “View Device
Info Menu (Device Information Menu)” on page 3–27.
Basic Menu
Purpose
Selecting Basic Menu takes you back to the basic menu of the MS2000 only.
Advanced menu items will no longer be visible on the System Control Panel.
When to use
Use this setting when you want to return to the basic menu of the MS2000.
Load sense
[On]
Value
Default
On
Off Off