Specifications
A–2
975-0466-01-01
Electrical Specifications
Input
Output
GT2.8-AU
GT5.0-AU
Input voltage, Maximum Power Point range
195 to 550 Vdc
240–550 Vdc
Absolute maximum array open circuit voltage
600 Vdc
Maximum input current
15.4 Adc
22 Adc
Maximum array short circuit current
24 Adc
Ground fault protection
Unit shut down if a high impedance
is not detected. See “PV Ground
Fault Detection” on page viii.
Recommended PV array power*
*These values can change depending on environmental conditions. To ensure
maximum power yield for your installation, the PV array size should be re-
viewed as part of the system design.
3070 W
5300 W
GT2.8-AU
GT5.0-AU
Maximum output power
2800 W ac
5000 W ac
Maximum output current
14.0 A
24.0 A
Nominal grid voltage
230 Vac
Nominal grid frequency
50 Hz
Total Harmonic Distortion (THD)
<3%
Power factor
>0.99% (at rated power)
>0.95% (full power range)
Output characteristics
Current source
Output current waveform
Sine wave